beautypg.com

9 supplement, 1 technical data, 9supplement – VEGA VEGABAR 17 User Manual

Page 24

background image

9

Supplement

9

.1 Technical data

General data

P

arameter, pressure

G

auge pressure, absolute pressure, vacuum

M

easuring principle

P

iezoresistive/Thin film DMS

C

ommunication interface

N

one

Materials and weights

M

aterials, wetted parts

-

P

rocess fitting

316T

i

-

D

iaphragm

316T

i

-

D

iaphragm with front flush version

316T

i, Hastelloy C4

-

S

eal, O-ring

FPM, FKM, EPDM, NBR

M

aterials, non-wetted parts

-

I

nternal transmission liquid

S

ynthetic oil, Halocarbon oil

2)3)

-

H

ousing

316T

i

-

T

erminal housing

316T

i

-

G

round terminal

316T

i

-

P

lug

PA

-

C

able gland

PA, 316T

i

-

P

lug seal

S

ilicone

-

C

onnection cable

PUR

A

vailable cable length max.

40

m

W

eight approx.

-

V

ersion with plug connector, cable outlet

0.2

kg (0.441 lbs)

-

V

ersion with terminal housing

0.35

kg (0.772 lbs)

T

orque max.

50 N

m (36.88 lbft)

Output variable

O

utput signal

4 … 20

mA

Z

ero and span adjustable via potentiometer

±

5 %

D

ead time

1

ms

S

tep response time (10 … 90 %)

-

S

tandard version

1

ms

2)

S

ynthetic oil: For measuring ranges up to 16 bar, FDA listed for the food

processing industry. For measuring ranges up to 25 bar not available.

3)

H

alocarbon oil: With version oil and greasefree, not with vacuum measuring

ranges, not with absolute measuring ranges < 1 bar

abs

.

24

VEGABAR

17

9 S

upplement

27636

-EN

-120531