beautypg.com

Service – American Magnetics 4Q12125PS-430 High Stability Integrated Power Supply System User Manual

Page 156

background image

138

Rev. 5

Service

Troubleshooting Hints

5.2.4 Power supply unstable - magnet voltage oscillates

Note

If the size of the voltage oscillation is small (approximately 0.1 volt

or smaller), see step 1, below. If the voltage oscillation is larger than

approximately 0.1 volt, see steps 1 through 4, below.

1. Adjust the persistent switch heater current to a value 10 mA larger

than the present value. If the oscillation stops, adjust the heater

current to as small a value as possible that maintains magnet

voltage stability.

2. Verify the power supply controlled by the Model 430 Programmer is

configured for remote programming, voltage-to-voltage mode.

Consult the manufacturer’s operations manual for the necessary

power supply configuration.

3. Verify that the persistent switch heater is operating. Also, verify

that the actual persistent switch in the magnet is correctly

installed and connected.

Note

If the persistent switch heater is activated without an inductive load

present at the supply outputs, oscillating current will result. The

Model 430 Programmer is designed to operate large inductive loads

with only relatively small resistive characteristics (i.e.

superconducting magnets). The Model 430 Programmer is not

designed for use as a general purpose power supply controller for

resistive loads.

4. If the magnet has no persistent switch installed, or has a small

inductance (typically less than 3 H), then adjust the stability

setting for the Model 430 Programmer. As this setting is increased,

the system should become more stable. For best results, minimize

the amount that this value is adjusted from 0.0%. Refer to section

3.10.2.1.

5.2.5 The power supply system will not charge the magnet.

1. Verify system interconnecting wiring. Refer to section 2.5. If the

Model 430 Programmer shows “+0.00 A ↑ Status: Ramping with

the supply voltage, Vs, increasing or at the programmed Voltage

Limit (as indicated by the reverse video “V” status indicator), there

may be a problem with the power supply. Verify the power supply is

on and the program out connection from the Model 430

Programmer to the program voltage input to the power supply is

intact.