Functional description

The FLM-420/4-CON Conventional interface module enables monitored connection of conventional detectors to LSN
fire panels via a 4-wire supply network (LSN with external power supply).
The surface-mount housing for the FLM-420/4-CON-S has pre-formed conduit connections and rubber bushings for
cable entries (Figure 2, page 7, Removal: Figure 1, page 6, Installation: Figure 5, page 9).
The FLM-420/4-CON-D is installed on a DIN rail in accordance with EN 500022 with enclosed adapter (Installation:
Figure 6, page 10; Removal: Figure 7, page 11).

Address setting
Fit a rotary switch in the required position using a pan head slotted screwdriver (see Figure 8, page 12).
X

It is not permitted to use different operating modes in one loop/stub/T branch next to each other!

Connection

Technical specifications

Address (A)

Operating mode

0 0 0

Loop/stub in LSN improved version mode with automatic addressing

0 0 1 ... 2 5 4 Loop/stub/T branches in LSN improved version mode with manual addressing

CL 0 0

Loop/stub in LSN classic mode (address range: max. 127)

2 5 5 ... 2 9 9 Non-permitted address range (error message on fire panel)!

Connection to LSN

See ...

With power supply via LSN additional power supply

Figure 10, page 13

With power supply via external power supply unit (free-of-ground)

Figure 11, page 13

Connection of conventional lines

See ...

2 stubs (Class B)

Figure 12, page 14, left

1 stub (Class B)

Figure 12, page 14, right

1 loop (Class A)

Figure 13, page 15

Description

Function

LSN: b1+ | a- | b2+

LSN b incoming / LSN a / LSN b outgoing

AUX: 2+ | 1/2- | 1+

Power supply output, 4-wire detector

OUT1: + | -

Stub 1 or outgoing loop

OUT2/IN1: - | +

Stub 2 or incoming loop

PWR IN
LSN AUX or EXT.PWR: + | -

Power supply input (from LSN or external)

* Does not apply if connecting 2-wire detectors

LSN

Input voltage

15 to 33 V DC (min. to max.)

Max. current consumption

8.5 mA

Primary line

Line voltage

21 to 22 V DC (21,5 V DC typ. ±0,5 V DC)

Max. line current

80 mA (±10% @ 25 °C)

Max. line resistance

50

Ω per line (2 x 25 Ω max.)

Power supply input (PWR IN) Voltage

24 to 30 V DC (min. to max.)

Ripple

< 150 mV

Power supply output, 4-wire
detector

Voltage

23.5 to 30 V DC (rated voltage 24 V DC)

Max. current

200 mA per output (can be switched in parallel)

Ripple

< 300 mV

EOL resistor for zone as stub (Class B)

With calibration value: 2,2 k

Ω

Without calibration value: 2,2 k

Ω / 3,9 kΩ

Permissible wire diameter

0.6 to 3.3 mm

2

Permissible operating temperature / storage temperature

-20 °C ... +55 °C / -25 °C ... +80 °C

Permissible relative humidity

<96%, non-condensing

Protection class as per IEC 60529

FLM-420/4-CON-S: IP 54
FLM-420/4-CON-D: IP 30

Safety class as per IEC 60950

III

EMC interference immunity/EMC emitted interference

EN 54-18, EN 50130, VDS 2540/EN 61000-6-3

Housing material and color

Surface-mount housing

ABS/PC blend, signal white (RAL 9003)

Interface housing and adapter

PPO (Noryl), gray white (similar to RAL 9002)

Dimensions

FLM-420/4-CON-S

approx. 126 mm x 126 mm x 71mm (W x H x D)

FLM-420/4-CON-D

approx. 110 mm x 110 mm x 48 mm (W x H x D)