Bosch FLM-420 User Manual
Page 19
FLM-420/4-CON Conventional Interface Module for 4-wire LSN
| en
19
Bosch Sicherheitssysteme GmbH
Installation Guide
F.01U.012.982 | 5.0 | 2008.12
Functional description
The FLM-420/4-CON Conventional interface module enables monitored connection of conventional detectors to LSN
fire panels via a 4-wire supply network (LSN with external power supply).
The surface-mount housing for the FLM-420/4-CON-S has pre-formed conduit connections and rubber bushings for
cable entries (Figure 2, page 7, Removal: Figure 1, page 6, Installation: Figure 5, page 9).
The FLM-420/4-CON-D is installed on a DIN rail in accordance with EN 500022 with enclosed adapter (Installation:
Figure 6, page 10; Removal: Figure 7, page 11).
Address setting
Fit a rotary switch in the required position using a pan head slotted screwdriver (see Figure 8, page 12).
X
It is not permitted to use different operating modes in one loop/stub/T branch next to each other!
Connection
Technical specifications
Address (A)
Operating mode
0 0 0
Loop/stub in LSN improved version mode with automatic addressing
0 0 1 ... 2 5 4 Loop/stub/T branches in LSN improved version mode with manual addressing
CL 0 0
Loop/stub in LSN classic mode (address range: max. 127)
2 5 5 ... 2 9 9 Non-permitted address range (error message on fire panel)!
Connection to LSN
See ...
With power supply via LSN additional power supply
With power supply via external power supply unit (free-of-ground)
Connection of conventional lines
See ...
2 stubs (Class B)
1 stub (Class B)
1 loop (Class A)
Description
Function
LSN: b1+ | a- | b2+
LSN b incoming / LSN a / LSN b outgoing
AUX: 2+ | 1/2- | 1+
Power supply output, 4-wire detector
OUT1: + | -
Stub 1 or outgoing loop
OUT2/IN1: - | +
Stub 2 or incoming loop
PWR IN
LSN AUX or EXT.PWR: + | -
Power supply input (from LSN or external)
* Does not apply if connecting 2-wire detectors
LSN
Input voltage
15 to 33 V DC (min. to max.)
Max. current consumption
8.5 mA
Primary line
Line voltage
21 to 22 V DC (21,5 V DC typ. ±0,5 V DC)
Max. line current
80 mA (±10% @ 25 °C)
Max. line resistance
50
Ω per line (2 x 25 Ω max.)
Power supply input (PWR IN) Voltage
24 to 30 V DC (min. to max.)
Ripple
< 150 mV
Power supply output, 4-wire
detector
Voltage
23.5 to 30 V DC (rated voltage 24 V DC)
Max. current
200 mA per output (can be switched in parallel)
Ripple
< 300 mV
EOL resistor for zone as stub (Class B)
With calibration value: 2,2 k
Ω
Without calibration value: 2,2 k
Ω / 3,9 kΩ
Permissible wire diameter
0.6 to 3.3 mm
2
Permissible operating temperature / storage temperature
-20 °C ... +55 °C / -25 °C ... +80 °C
Permissible relative humidity
<96%, non-condensing
Protection class as per IEC 60529
FLM-420/4-CON-S: IP 54
FLM-420/4-CON-D: IP 30
Safety class as per IEC 60950
III
EMC interference immunity/EMC emitted interference
EN 54-18, EN 50130, VDS 2540/EN 61000-6-3
Housing material and color
Surface-mount housing
ABS/PC blend, signal white (RAL 9003)
Interface housing and adapter
PPO (Noryl), gray white (similar to RAL 9002)
Dimensions
FLM-420/4-CON-S
approx. 126 mm x 126 mm x 71mm (W x H x D)
FLM-420/4-CON-D
approx. 110 mm x 110 mm x 48 mm (W x H x D)