Table 6: cooling capacity 10 ton unit - imperial – York PREDATOR DM150 User Manual
Page 16
036-21044-003-A-0304
16
Unitary Products
TABLE 6: COOLING CAPACITY 10 TON UNIT - IMPERIAL
Air On
Evap. Coil
Temperature of Air on Condenser Coil 85°F
Temperature of Air on Condenser Coil 95°F
CFM
WB
(°F)
Tot.
Cap.
1
(MBH)
Tot.
Input
2
(kW)
Sensible Capacity (MBH)
1
Return Dry Bulb (°F)
Tot.
Cap.
1
(MBH)
Tot.
Input
2
(kW)
Sensible Capacity (MBH)
1
Return Dry Bulb (°F)
86
83
80
77
74
71
68
86
83
80
77
74
71
68
3000
72
148
11.2
82
73
65
56
48
-
-
137
12.0
79
71
62
54
45
-
-
67
134
10.8
102
94
85
77
68
60
51
124
11.6
98
90
81
73
64
56
47
62
125
10.5
121
112
103
95
86
78
69
115
11.2
115
110
101
93
84
75
67
57
123
10.6
123
116
107
99
90
82
73
110
11.4
110
110
101
93
84
76
67
3500
72
149
11.4
89
79
69
59
49
-
-
139
12.2
86
76
66
56
46
-
-
67
136
11.0
111
101
91
81
71
61
51
126
11.7
106
96
86
76
66
56
46
62
126
10.6
124
120
110
100
90
80
70
117
11.4
117
114
107
97
87
77
67
57
124
10.7
124
120
114
104
94
84
74
112
11.5
112
112
107
97
87
77
67
4000
72
150
11.6
97
85
74
62
50
-
-
141
12.4
93
82
70
58
47
-
-
67
137
11.2
120
108
97
85
73
62
50
128
11.9
115
103
91
80
68
56
45
62
127
10.8
127
127
117
106
94
82
71
119
11.5
119
119
113
102
90
78
67
57
125
10.9
125
125
122
110
98
87
75
113
11.7
113
113
113
102
90
78
67
4500
72
153
11.7
105
92
78
65
52
-
-
143
12.4
103
90
76
63
50
-
-
67
139
11.3
130
116
103
90
76
63
50
129
12.0
122
113
100
86
73
60
47
62
130
10.9
130
130
125
111
98
85
72
120
11.6
120
120
117
104
91
78
64
57
127
11.0
127
127
125
112
99
86
72
115
11.7
115
115
115
101
88
75
61
5000
72
156
11.7
113
98
83
68
53
-
-
144
12.5
113
98
83
68
53
-
-
67
141
11.4
139
124
109
94
79
65
50
130
12.1
130
123
108
93
79
64
49
62
132
11.0
132
132
132
117
102
87
72
122
11.7
122
122
122
107
92
77
62
57
129
11.1
129
129
129
114
100
85
70
116
11.8
116
116
116
101
86
71
56
Temperature of Air on Condenser Coil 105°F
Temperature of Air on Condenser Coil 115°F
3000
72
129
12.8
75
67
58
50
41
-
-
122
13.5
71
63
54
46
37
-
-
67
114
12.3
94
86
77
68
60
51
43
105
13.0
90
81
73
64
56
47
38
62
109
11.9
109
103
95
86
78
69
61
102
12.6
102
97
89
80
72
63
55
57
104
12.1
104
102
93
84
76
67
59
98
12.8
98
93
85
76
68
59
51
3500
72
130
13.0
82
72
62
52
42
-
-
122
13.7
78
68
58
48
38
-
-
67
115
12.5
102
92
82
72
62
52
42
105
13.2
97
88
78
68
58
48
38
62
110
12.1
110
107
101
91
81
71
61
102
12.8
102
100
95
85
75
65
55
57
105
12.3
105
103
99
89
79
69
59
97
13.0
97
95
91
81
71
61
51
4000
72
131
13.1
89
78
66
54
43
-
-
121
13.9
85
74
62
51
39
-
-
67
116
12.7
110
99
87
76
64
52
41
105
13.4
105
95
83
72
60
48
37
62
111
12.3
111
111
108
96
84
73
61
102
13.0
102
102
102
90
79
67
55
57
105
12.4
105
105
105
94
82
70
59
97
13.2
97
97
97
86
74
62
51
4500
72
133
13.2
98
85
72
58
45
-
-
124
14.0
94
80
67
54
40
-
-
67
118
12.7
115
108
95
82
68
55
42
107
13.5
107
102
90
77
63
50
37
62
112
12.4
112
112
111
98
84
71
58
104
13.1
104
104
104
91
78
64
51
57
107
12.5
107
107
107
94
80
67
54
99
13.3
99
99
99
86
73
60
46
5000
72
135
13.3
107
92
77
63
48
-
-
127
14.1
102
87
72
57
42
-
-
67
120
12.8
120
116
102
87
73
58
43
110
13.6
110
110
96
82
67
52
37
62
114
12.5
114
114
114
99
84
69
54
106
13.2
106
106
106
92
77
62
47
57
109
12.6
109
109
109
94
79
64
49
102
13.4
102
102
102
87
72
57
42
Temperature of Air on Condenser Coil 125°F
3000
72
115
14.2
67
59
50
42
33
-
-
67
96
13.7
85
77
68
60
51
43
34
62
96
13.3
96
91
83
74
66
57
48
57
92
13.5
92
85
77
68
59
51
42
3500
72
113
14.5
74
64
54
44
34
-
-
67
95
13.9
93
84
74
64
54
44
33
62
95
13.5
95
92
89
79
69
59
49
57
90
13.8
90
87
83
73
63
53
42
4000
72
112
14.7
82
70
58
47
35
-
-
67
94
14.2
94
91
79
68
56
44
33
62
93
13.8
93
93
93
84
73
61
49
57
89
14.0
89
89
89
77
66
54
43
4500
72
115
14.8
89
76
62
49
36
-
-
67
96
14.3
96
96
85
72
58
45
32
62
96
13.8
96
96
96
84
71
58
44
57
92
14.1
92
92
92
79
65
52
39
5000
72
118
14.9
96
81
66
51
37
-
-
67
99
14.4
99
99
90
76
61
46
31
62
99
13.9
99
99
99
84
69
54
39
57
95
14.2
95
95
95
80
65
50
35
1 These capacities are gross ratings. For net
capacity, deduct air blower motor, MBH = 3.415
x kW. Refer to the appropriate Blower Perfor-
mance Table for the kW of the supply air
blower motor.
2 These ratings include condenser fan motors
and the compressor motors but not the supply
air blower motor.