Lo ac freq, Hi ac volt, Lo ac freq –25 hi ac volt –25 – Xantrex Technology RS3000 User Manual
Page 75
Configuration
975-0170-01-01
3–25
Lo AC Freq
Full name
Low AC transfer frequency (AC under frequency level)
Configurable setting
This setting lets you adjust the lowest frequency at which the
inverter/charger no longer qualifies AC as “good” and attempts to transfer
to invert mode.
You can adjust Lo AC Freq settings as follows:
When to use
This setting can be used when the AC supply frequency is lower than the
set value required for the electrical equipment.
Outcome
The lower frequency of the AC supply above which it will be qualified as
“good” by the inverter/charger can be varied.
Hi AC Volt
Full name
High AC transfer voltage (AC over voltage level)
Configurable setting
This setting lets you adjust the voltage above which the inverter/charger
no longer qualifies AC as “good” and transfers to Invert.
You can adjust Hi AC Volt settings as follows:
When to use
This setting lets you adjust the AC parameters when AC supply is outside
the upper voltage range required for electrical equipment.
Outcome
The upper limit of the voltage that will be qualified as “good” by the
inverter/charger can be varied.
Lo AC Freq
[55Hz]
Range of values
Increment
Default
55 to 58 Hz
1 Hz
55 Hz
Hi AC Volt
[135V]
Range of values
Increment
Default
120 to 145 VAC
1 volt
135 VAC