Features – York SUNLINE MAGNUM DJ 240 User Manual
Page 8
036-21410-001-A-0502
8
Unitary Products Group
FEATURES
All models are available with a wide variety of factory-
mounted options such as stainless steel heat exchangers,
phase monitor, dirty filter switch, and coil guard to make them
suitable for almost every application.
All units are self-contained and assembled on full perimeter
base rails with holes in the four corners for overhead rigging.
Every unit is completely piped, wired, charged and tested at
the factory to simplify the field installation and to provide
years of dependable operation.
All models (including those with an economizer) are suitable
for either bottom or horizontal duct connections. Models with
factory installed power exhaust are suitable for bottom
duct connections only. For bottom duct, you remove the
sheet metal panels from the supply and return air openings
through the base of the unit. For horizontal duct, you replace
the supply and return air panels on the rear of the unit with a
side duct flange accessory.
All models are available with these “factory mounted” outdoor
air damper options:
•
Single enthalpy economizer
•
Single enthalpy economizer with power exhaust
•
Motorized outdoor air damper
A fixed outdoor air intake assembly will be shipped in the
return air compartment of all units ordered without an econo-
mizer or motorized outdoor air damper option. The assembly
includes a rain hood with a damper that can be set for 10, 15
or 25% outdoor air. With bottom duct connections, the intake
damper assembly should be mounted over the opening in the
return air panel. With horizontal ductwork, it should be
mounted on the return air duct.
All supply air blowers are equipped with a belt drive that can
be adjusted to meet the exact requirements of the job. A high
static drive option is available for applications with a higher
CFM and/or static pressure requirement.
All compressors include scroll compressors and internal pres-
sure relief. Every refrigerant circuit includes an expansion
valve, a liquid line filter-drier, a discharge line high pressure
switch and a suction line with a freezestat and low pressure/
loss of charge switch to protect all system components.
•
Simplicity™ Controls - Simplicity™ control boards
have standardized a number of features previously avail-
able only as options or by utilizing additional controls.
•
Low Ambient - An integrated low-ambient control
allows all units to operate in the cooling mode down
to 0ºF outdoor ambient without additional assis-
tance. Optionally, the control board can be pro-
grammed to lockout the compressors when the
outdoor air temperature is low or when free cooling
is available.
•
Anti-Short Cycle Protection - To aid compressor
life, an anti-short cycle delay is incorporated into the
standard controls. Compressor reliability is further
ensured by programmable minimum run times. For
testing, the anti short cycle delay can be temporarily
overridden with the push of a button.
•
Fan Delays - Fan on and fan off delays are fully pro-
grammable. Furthermore, the heating and cooling
fan delay times are independent of one another. All
units are programmed with default values based
upon their configuration of cooling and heat.
•
Safety Monitoring - The control board monitors the
high and low-pressure switches, the freezestats, the
gas valve, if applicable, and the temperature limit
switch on gas and electric heat units. The unit con-
trol board will alarm on ignition failures, compressor
lockouts and repeated limit switch trips.
•
Nuisance Trip Protection and Strikes - To prevent
nuisance trouble calls, the control board uses a
“three times, you’re out” philosophy. The high and
low-pressure switches and the freezestats must trip
three times within two hours before the unit control
board will lock out the associated compressor.
•
On Board Diagnostics - Each alarm will energize a
trouble light on the thermostat, if so equipped, and
flash an alarm code on the control board LED. Each
high and low-pressure switch alarm as well as each
freezestat alarm has its own flash code. The control
board saves the five most recent alarms in memory,
and these alarms can be reviewed at any time.
Alarms and programmed values are retained
through the loss of power.
All units have long lasting powder paint cabinets with 750
hour salt spray test approval under ASTM-B117 procedures.
All models are CSA approved.
•
Warranty - All models include a one-year limited parts
warranty on the complete unit. Compressors and electric
heater elements carry a five-year warranty. Gas heat
exchangers carry a 10-year parts warranty.
•
Gas Heat Operation - All gas heat units are built with
two heating sections for two equal stages of capacity
control. Each section includes a durable heat exchanger
with aluminized steel or optional stainless steel tubes, a
redundant gas valve, spark ignition, power venting, an
ignition module for 100% shut-off and all of the safety
controls required to meet the latest ANSI standards.
The gas supply piping can be routed into the heating
compartment through a hole in the base pan of the unit
or through a knockout in the piping panel on the front of
the unit.