036-21410-001-A-0502

30

Unitary Products Group

TABLE 21: COOLING CAPACITIES FOR DJ300 AT 105°F

RETURN AIR

OUTDOOR AMBIENT TEMPERATURE (°F): 105

CFM

WB

TEMP °F

GROSS

CAPACITY

1

(MBH)

INPUT

POWER

2

(kW)

GROSS SENSIBLE CAPACITY

1

(MBH)

(RETURN AIR DRY BULB TEMP. - (°F) )

86

83

80

77

74

71

68

7500

72

301.8

27.73

184.5

163.2

141.8

120.4

99.0

#N/A

#N/A

67

289.0

27.27

238.8

217.4

196.0

174.6

153.2

131.9

110.5

62

283.6

26.57

280.8

259.7

238.3

216.9

195.5

174.1

152.7

57

271.5

26.43

271.5

260.3

238.9

217.6

196.2

174.8

153.4

8750

72

306.8

27.83

201.3

176.1

150.8

125.5

100.2

#N/A

#N/A

67

293.9

27.37

259.0

233.7

208.5

183.2

157.9

132.7

107.4

62

288.3

26.67

286.9

276.4

253.4

228.1

202.8

177.6

152.3

57

276.1

26.53

276.1

270.5

254.1

228.8

203.5

178.3

153.0

10000

72

311.8

27.93

218.1

188.9

159.8

130.6

101.5

#N/A

#N/A

67

298.7

27.47

279.3

250.1

220.9

191.8

162.6

133.5

104.3

62

293.1

26.77

293.1

293.1

268.5

239.3

210.2

181.0

151.9

57

280.6

26.63

280.6

280.6

269.2

240.0

210.9

181.7

152.6

11250

72

318.7

28.19

233.1

199.9

166.7

133.5

100.3

#N/A

#N/A

67

305.4

27.73

294.9

263.7

230.5

197.3

164.1

130.9

97.7

62

299.6

27.02

299.6

299.6

280.1

246.9

213.7

180.5

147.3

57

286.8

26.88

286.8

286.8

280.9

247.7

214.5

181.2

148.0

12500

72

325.6

28.46

248.2

210.9

173.6

136.4

99.1

#N/A

#N/A

67

312.0

27.99

310.5

277.4

240.1

202.8

165.6

128.3

91.1

62

306.0

27.27

306.0

306.0

291.8

254.5

217.3

180.0

142.8

57

293.0

27.13

293.0

293.0

292.5

255.3

218.0

180.8

143.5

1. The capacities are gross ratings. For net capacity, deduct the supply air blower motor heat, MBH = 3.415 x kW. Refer to the appro-

priate blower performance table for the kW of the supply air blower motor.

2. These ratings include condenser fan motor and compressor motor power but not the supply air blower motor power.

This manual is related to the following products: