beautypg.com

Typical applications with mc multi-position coils, Cooling models with electric heat, Control wiring - mv series – York MV User Manual

Page 11

background image

255427-YTG-F-1006

Unitary Products Group

11

APPLICATION FACTORS - RATED CFM VS. ACTUAL CFM

% OF RATED AIR FLOW

80%

90%

RATED CFM

110%

120%

CAPACITY FACTOR

0.96

0.98

1.00

1.02

1.03

Typical Applications with MC Multi-Position Coils

Up Flow

Down Flow

Horizontal Right

Horizontal Left

COOLING MODELS WITH ELECTRIC HEAT

MA SERIES - Air Handler Control Wiring

Typical A/C - Cooling only Applications

THERMOSTAT

AIR HANDLER

BOARD

1 - STAGE

AIR CONDITIONING

R

R

G

Y

W1

W2

C

G

W1

W2

Y

C

Y / Y2

Y1

O

HUM

X / L

COM

HUMIDISTAT *

THERMOSTAT

AIR HANDLER

BOARD

1 - STAGE

AIR CONDITIONING

R

R

G

Y

W1

W2

C

G

W1

W2

Y

C

Y / Y2

Y1

O

HUM

X / L

COM

HUMIDISTAT *

MA SERIES - Air Handler Control Wiring

Typical A/C with Electric Heat Applications

CONTROL WIRING - MV SERIES

CONTROL WIRING - MA Series - Air Handler & New UPG HP Systems

Two Stage H/P with York Guard VI Board & Copeland “Ultra Tech”

Conventional Application - Not Hot Heat Pump

THERMOSTAT

AIR HANDLER

BOARD

2 - STAGE SCROLL

HEAT PUMP

R

R

R

G

G

Y2

E

W

W

O

O

O

X / L

X / L

X / L

C

C

Y / Y2

Y1

Y1

Y2 OUT

Y2

W2 OUT

W1 OUT

BS

W2

W1

HUM

COM

HUMIDISTAT *

Y1