COOLING AIRFLOW DATA - MV MODELS

HIGH / LOW SPEED COOLING AND HEAT PUMP CFM

12B Air Handler

12D Air Handler

JUMPER SETTINGS

CFM

m

3

/min

CFM

m

3

/min

High

Low

High

Low

High

Low

High

Low

COOL Tap

ADJ Tap*

1307

882

37.0

25.0

1366

869

38.7

24.6

A

B

1080

756

30.6

21.4

1097

717

31.1

20.3

B

B

1270

862

36.0

24.4

1312

856

37.2

24.2

A

A

943

689

26.7

19.5

957

646

27.1

18.3

B

A

1146

786

32.5

22.3

1167

761

33.0

21.5

A

C

1050

726

29.7

20.6

1051

703

29.8

19.9

C

B

870

632

24.6

17.9

863

580

24.4

16.4

B

C

771

594

21.8

16.8

739

520

20.9

14.7

D

B

931

668

26.4

18.9

927

629

26.2

17.8

C

A

693

565

19.6

16.0

658

495

18.6

14.0

D

A

851

624

24.1

17.7

830

567

23.5

16.1

C

C

655

567

18.5

16.1

594

488

16.8

13.8

D

C

16C Air Handler

20D Air Handler

JUMPER SETTINGS

CFM

m

3

/min

CFM

m

3

/min

High

Low

High

Low

High

Low

High

Low

COOL Tap

ADJ Tap*

1920

1321

54.4

37.4

2209

1394

62.6

39.5

A

B

1699

1189

48.1

33.7

2022

1394

57.3

39.5

B

B

1884

1296

53.3

36.7

2178

1381

61.7

39.1

A

A

1558

1094

44.1

31.0

1798

1378

50.9

39.0

B

A

1714

1193

48.5

33.8

1965

1226

55.6

34.7

A

C

1451

1037

41.1

29.4

1843

1143

52.2

32.4

C

B

1403

1009

39.7

28.6

1596

1226

45.2

34.7

B

C

1288

947

36.5

26.8

1700

1066

48.1

30.2

D

B

1336

978

37.8

27.7

1608

1023

45.5

29.0

C

A

1214

888

34.4

25.1

1493

967

42.3

27.4

D

A

1239

915

35.1

25.9

1430

911

40.5

25.8

C

C

1098

839

31.1

23.8

1334

877

37.8

24.8

D

C

All CFM’s are shown at 0.5” w.c. external static pressure.These units have variable speed motors that automatically adjust to provide constant CFM from 0.0” to
0.6” w.c. static pressure. From 0.6” to 1.0” static pressure, CFM is reduced by 2% per 0.1” increase in static. Operation on duct systems with greater than 1.0” w.c.
external static pressure is not recommended.
NOTE: At some settings, LOW COOL and/or LOW HEAT airflow may be lower than what is required to operate an airflow switch on certain models of electronic air
cleaners. Consult the instructions for the electronic air cleaner for further details.
* The ADJ “D” tap should not be used.

HEATING AIRFLOW DATA - MV MODELS

HIGH / LOW SPEED COOLING AND HEAT PUMP CFM

12B Air Handler

12D Air Handler

JUMPER SETTINGS

CFM

m

3

/min

CFM

m

3

/min

High

Low

High

Low

High

Low

High

Low

COOL Tap

ADJ Tap*

1270

791

36.0

22.4

1312

762

37.2

21.6

A

A

943

714

26.7

20.2

957

668

27.1

18.9

B

A

931

643

26.4

18.2

927

591

26.2

16.7

C

A

693

567

19.6

16.1

658

488

18.6

13.8

D

A

16C Air Handler

20D Air Handler

JUMPER SETTINGS

CFM

m

3

/min

CFM

m

3

/min

High

Low

High

Low

High

Low

High

Low

COOL Tap

ADJ Tap*

1884

1217

53.3

34.5

2178

1217

61.7

34.5

A

A

1558

1065

44.1

30.2

1798

1036

50.9

29.3

B

A

1336

823

37.8

23.3

1608

748

45.5

21.2

C

A

1214

727

34.4

20.6

1493

551

42.3

15.6

D

A

All CFM’s are shown at 0.5” w.c. external static pressure.These units have variable speed motors that automatically adjust to provide constant CFM from 0.0” to
0.6” w.c. static pressure. From 0.6” to 1.0” static pressure, CFM is reduced by 2% per 0.1” increase in static. Operation on duct systems with greater than 1.0” w.c.
external static pressure is not recommended.
NOTE: At some settings, LOW COOL and/or LOW HEAT airflow may be lower than what is required to operate an airflow switch on certain models of electronic air
cleaners. Consult the instructions for the electronic air cleaner for further details.
* The ADJ “D” tap should not be used.