Caution: reverse polarity – Xantrex Technology FREEDOM HW 1000 User Manual
Page 32
1–20
975-0468-01-01
This guide for use by qualified installers only
11. Insert the Line and Neutral wires into the corresponding terminals.
12. Tighten the wire attachment screws to a torque of 15.6–21.6 in-lbf
(1.76–2.44 N-m). Leave some wiring slack inside the wiring
compartment.
Ensure you have maintained correct polarity and that there are no
loose strands of wire.
13. Reinstall the AC wiring compartment cover.
14. Connect the outgoing AC wires to the AC load panel.
CAUTION: Reverse polarity
Improper connections (connecting a line conductor to a neutral conductor, for
example) will cause the Freedom HW to malfunction and may permanently
damage the inverter. Damage caused by a reverse polarity connection is not
covered by your warranty.