York SUNLINE MAGNUM DY 036 User Manual
Page 9
343615-YTG-D-0708
Johnson Controls Unitary Products
9
TABLE 4:
DY036 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED INLET)
UNIT DESCRIPTION / MODEL
CONFIGURATION
Indoor Blower Speed (RPM)
Blower Static Pressure (IWG)
Airflow (CFM)
Blower Motor BHP
63
80
82
80
82
78
83
81
85
125
76
77
76
77
82
83
81
82
250
56
59
56
60
60
61
58
60
500
50
50
49
50
54
54
51
52
1000
40
43
39
42
49
50
44
45
2000
41
42
40
42
49
49
43
44
4000
41
41
41 41
49 49 41 41
8000
45
45
45
45
47
47
45
45
DY036 / 3 Ton
Horizontal Ducted Inlet
630
631
879
885
0.2
0.3
0.2
0.7
1116
928
1979
1020
0.41
0.37
0.76
0.53
Octave Center Freq.
ID Blower
Only (dB)
Cooling
Operation
2
(dB)
ID Blower
Only (dB)
4. Test duct termination is flush with reverberation room wall.
5. Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.
Cooling
Operation
2
(dB)
1. Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment .
2. Cooling Operation – ID blower, compressor and outdoor fan operating.
3. Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).
Cooling
Operation
2
(dB)
ID Blower
Only (dB)
Cooling
Operation
2
(dB)
ID Blower
Only (dB)
TABLE 5:
DY036 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED DISCHARGE)
UNIT DESCRIPTION / MODEL
CONFIGURATION
Indoor Blower Speed (RPM)
Blower Static Pressure (IWG)
Airflow (CFM)
Blower Motor BHP
63
80
84
80
83
85
87
84
87
125
74
77
74
76
80
82
80
83
250
58
61
58
61
68
68
63
65
500
48
51
47
50
58
58
53
54
1000
41
45
39
43
55
55
49
50
2000
39
41
37
39
53
53
46
47
4000
41
41
38
38
55
55
49
49
8000
45
45
44
44
52
53
47
47
4. Test duct termination is flush with reverberation room wall.
5. Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.
Cooling
Operation
2
(dB)
1. Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment .
2. Cooling Operation – ID blower, compressor and outdoor fan operating.
3. Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).
Cooling
Operation
2
(dB)
ID Blower
Only (dB)
Cooling
Operation
2
(dB)
ID Blower
Only (dB)
Octave Center Freq.
ID Blower
Only (dB)
Cooling
Operation
2
(dB)
ID Blower
Only (dB)
0.41
0.37
0.76
0.53
1116
928
1979
1020
0.2
0.3
0.2
0.7
DY036 / 3 Ton
Horizontal Ducted Discharge
630
631
879
885