25 dy physical data, 26 electric heat correction factors, 27 voltage limitations – York SUNLINE MAGNUM DY 036 User Manual
Page 24
343615-YTG-D-0708
24
Johnson Controls Unitary Products
TABLE 25: DY PHYSICAL DATA
MODELS
DY
036
048
060
EVAPORATOR
BLOWER
Centrifugal Blower (Dia. x Wd. in.)
12 X 10
12 X 10
12 X 10
Fan Motor HP (Direct Drive)
3/4
1
1
EVAPORATOR
COIL
Rows Deep
3
4
4
Fins Per Inch
13
13
13
Face Area (Ft.
2
)
5.1
5.1
5.1
CONDENSER
FANS
Propeller Dia. (in.)
24
24
24
Fan Motor HP
1/2
1/2
1/2
Nom. CFM
4200
4200
4200
CONDENSER
COILS
Rows Deep
2
2
2
Fins Per Inch
18
18
18
Face Area (Ft.
2
)
17.1
17.1
17.1
COMPRESSOR
Quantity
1
1
1
Type
Recip.
Recip.
Scroll
AIR
FILTERS
Quantity Per Unit (15” X 20” X 1” or 2“)
2
2
2
Quantity Per Unit (14” X 25” X 1” or 2“)
1
1
1
Total Face Area (Ft.
2
)
6.3
6.3
6.3
CHARGE
Refrigerant 22 (lbs./oz.)
9/4
9/8
11/8
TABLE 26: ELECTRIC HEAT CORRECTION FACTORS
NOMINAL VOLTAGE
VOLTAGE
kW CAP. MULTI-
PLIER
208
208
1.00
240
230
0.92
480
460
0.92
600
575
0.92
TABLE 27: VOLTAGE LIMITATIONS
1
1. Utilization Range “A” in accordance with ARI Standard
110.
POWER SUPPLY
VOLTAGE
MIN.
MAX.
208/230-1-60
187
252
208/230-3-60
187
252
460-3-60
432
504
575-3-60
540
630