Table 22: keu electrical data (continued) – York EVAPORATOR BLOWERS K2EU060 User Manual
Page 23
036-21300-002-A-0905
Unitary Products Group
23
TABLE 22: KEU ELECTRICAL DATA (CONTINUED)
Model
(TONS)
Power
Supply
Voltage
Indoor
Motor
FLA
Heater
Model
Number
Nominal
Heater
KW
Applied
Heater KW
Electric
Heat Amps
Min.
Circuit
Ampacity
(AMPS)
Max. Fuse
1
/
HACR
Breaker
2
(AMPS)
180
(15)
208
10.6
None
--
--
--
13.3
20
2HS04501025
10
7.5
20.8
39.3
40
2HS04501625
16
12.0
33.4
54.9
60
2HS04502625
26
19.5
54.2
81.0
90
2HS04503625
36
27.0
75.1
107.1
110
2HS04507225
72
54.1
150.1
200.9
225
240
9.6
None
--
--
--
12.0
15
2HS04501025
10
10.0
24.1
42.1
45
2HS04501625
16
16.0
38.5
60.1
70
2HS04502625
26
26.0
62.5
90.2
100
2HS04503625
36
36.0
86.6
120.3
125
2HS04507225
72
72.0
173.2
228.5
250
460
4.8
None
--
--
--
6.0
15
2HS04501046
10
10.0
12.0
21.0
25
2HS04501646
16
16.0
19.2
30.1
35
2HS04502646
26
26.0
31.3
45.1
50
2HS04503646
36
36.0
43.3
60.1
70
2HS04507246
72
72.0
86.6
114.3
125
575
3.9
None
--
--
--
4.9
15
2HS04501058
10
10.0
9.6
16.9
20
2HS04501658
16
16.0
15.4
24.1
25
2HS04502658
26
26.0
25.0
36.1
40
2HS04503658
36
36.0
34.6
48.2
50
2HS04507258
72
72.0
69.3
91.5
100
1. Dual element time delay.
2. HACR type per NEC.
3. The K*EU060 indoor motor is single phase. The electrical heaters MUST be supplied with 3-phase voltage only.