Table 17: application data, Figure 3 - center of gravity and weights, Figure 4 - unit clearances – York CHAMPION ULTRA BHP024 User Manual
Page 18

036-21528-003-A-0703
18
Unitary Products Group
TABLE 17: APPLICATION DATA
MODEL
BHP
024
030
036
042
048
MINIMUM AIR FLOW
(CFM)
COOLING
800
1000
1050
1300
1500
HEATING
800
1000
1050
1400
1400
MAXIMUM AIR FLOW
(CFM)
COOLING
900
1125
1200
1400
1600
HEATING
900
1125
1200
1500
1600
MINIMUM OPERATING TEMPERATURE IN COOLING MODE
(AMBIENT, °F)
45
45
45
45
45
MIMINIM MIXED AIR IN COOLING MODE
(RETURN AIR, DB °F/WB °F)
68 / 57
68 / 57
68 / 57
68 / 57
68 / 57
MINIMUM MIXED AIR IN HEATING MODE
(RETURN AIR, °F)
55
55
55
55
55
FIGURE 3 - CENTER OF GRAVITY AND WEIGHTS
26
23
47
!"
CENTER OF GRAVITY
FRONT
OF
UNIT
49
&
A
B
C
D
B1HP
UNIT
SIZE
SHIPPING
WEIGHT
OPERATING
WEIGHT
CORNER WEIGHTS
A
B
C
D
024
356
351
97
93
81
84
030
353
348
96
93
81
84
036
388
383
106
102
89
92
042
440
435
120
115
101
104
048
485
480
132
127
111
115
FIGURE 4 - UNIT CLEARANCES
CLEARANCES
NOTE: FOR UNITS APPLIED WITH A ROOF CURB, THE
MINIMUM CLE ARANCE MAY BE REDUCED FROM 1
INCH TO 1/2 INCH BETWEEN COMBUSTIBLE ROOF
CURB MATERIAL AND THE SUPPLY DUCT.
UNIT CLEARANCES
(MINIMUM)
Front
12”
Back
0”
Left Side (Filter Access)
24”
Right Side
24”
Below Unit
1
1.
Units may be installed on combustible floors made from
wood or class A, B or C roof covering.
0”
Above Unit
2
2.
Units must be installed outdoors. Overhanging structures
or shrubs should not obstruct outdoor air discharge outlet.
36” (For Condenser
Air Discharge)
3'
MINIMUM CLEARANCE OF 1"
ALL SIDES FOR THE FIRST 3'
OF DUCT FOR 20 & 25 kW.
ZERO INCHES THEREAFTER,
FOR ALL OTHER HEATERS,
ZERO INCH CLEARANCE ALL
SIDES FOR ENTIRE LENGTH
OF DUCT.
FLEXIBLE DUCT
COLLAR