Application data, Center of gravity and weights, Unit clearances – York AFFINITY BHP024 User Manual
Page 19: Table 19: application data, Figure 3 - center of gravity and weights, Figure 4 - unit clearances, Clearances
036-21528-007-A-1205
Unitary Products Group
19
TABLE 19: APPLICATION DATA
MODEL
BHP
024
030
036
042
048
060
MINIMUM AIR FLOW
(CFM)
COOLING
800
1000
1050
1300
1500
1500
HEATING
800
1000
1050
1400
1400
1500
MAXIMUM AIR FLOW
(CFM)
COOLING
900
1125
1200
1400
1600
2050
HEATING
900
1125
1200
1500
1600
2050
MINIMUM OPERATING TEMPERATURE IN COOLING MODE
(AMBIENT, °F)
45
45
45
45
45
45
MIMINIM MIXED AIR IN COOLING MODE
(RETURN AIR, DB °F/WB °F)
68 / 57
68 / 57
68 / 57
68 / 57
68 / 57
68 / 57
MINIMUM MIXED AIR IN HEATING MODE
(RETURN AIR, °F)
55
55
55
55
55
55
FIGURE 3 - CENTER OF GRAVITY AND WEIGHTS
49-1/8
26
23-1/2
47-1/4
A
B
C
D
FRONT
OF
UNIT
CENTER OF GRAVITY
B1HP
UNIT
SIZE
SHIPPING
WEIGHT
OPERATING
WEIGHT
CORNER WEIGHTS
A
B
C
D
024
356
351
97
93
81
84
030
353
348
96
93
81
84
036
388
383
106
102
89
92
042
440
435
120
115
101
104
048
485
480
132
127
111
115
060
495
490
135
130
113
117
FIGURE 4 - UNIT CLEARANCES
CLEARANCES
NOTE: FOR UNITS APPLIED WITH A ROOF CURB, THE
MINIMUM CLE ARANCE MAY BE REDUCED FROM 1
INCH TO 1/2 INCH BETWEEN COMBUSTIBLE ROOF
CURB MATERIAL AND THE SUPPLY DUCT.
UNIT CLEARANCES
(MINIMUM)
Front
12”
Back
0”
Left Side (Filter Access)
24”
Right Side
24”
Below Unit
1
1.
Units may be installed on combustible floors made from
wood or class A, B or C roof covering.
0”
Above Unit
2
2.
Units must be installed outdoors. Overhanging structures
or shrubs should not obstruct outdoor air discharge outlet.
36” (For Condenser
Air Discharge)
3'
M IN IM U M C LEAR AN C E O F 1 "
ALL S ID ES F O R T H E F IR ST 3 '
O F D U C T F O R 2 0 & 2 5 k W .
ZER O IN C H ES T H ER EAFTER ,
FO R A LL O TH ER H EATER S,
ZER O IN C H C LEAR AN C E A LL
SID ES F O R E N TIRE L EN G TH
O F D U C T.
FLEXIBLE D U C T
C O LLAR