TABLE 11: HEATING CAPACITIES - 3 TON (BHP036)

CFM

RETURN

AIR °F

CAP

1

& KW

OUTDOOR AIR TEMPERATURE, °F (72% RH)

-10

0

10

20

30

40

50

60

900

55

MBH

10.597

12.792

15.448

18.660

22.545

27.244

32.929

39.804

KW

1.791

1.898

2.005

2.112

2.219

2.326

2.433

2.540

70

MBH

9.420

11.615

14.271

17.483

21.368

26.067

31.752

38.627

KW

2.198

2.305

2.412

2.519

2.626

2.733

2.840

2.947

80

MBH

7.543

9.738

12.394

15.606

19.491

24.190

29.875

36.750

KW

2.476

2.583

2.690

2.797

2.904

3.011

3.118

3.225

1200

55

MBH

11.652

13.847

16.503

19.715

23.600

28.299

33.984

40.859

KW

1.825

1.932

2.039

2.146

2.253

2.360

2.467

2.574

70

MBH

10.475

12.670

15.326

18.538

22.423

27.122

32.807

39.682

KW

2.232

2.339

2.446

2.553

2.660

2.767

2.874

2.981

80

MBH

8.598

10.793

13.449

16.661

20.546

25.245

30.930

37.805

KW

2.510

2.617

2.724

2.831

2.938

3.045

3.152

3.259

1500

55

MBH

12.282

14.477

17.133

20.345

24.230

28.929

34.614

41.489

KW

1.779

1.886

1.993

2.100

2.207

2.314

2.421

2.528

70

MBH

11.105

13.300

15.956

19.168

23.053

27.752

33.437

40.312

KW

2.186

2.293

2.400

2.507

2.614

2.721

2.828

2.935

80

MBH

9.228

11.423

14.079

17.291

21.176

25.875

31.560

38.435

KW

2.464

2.571

2.678

2.785

2.892

2.999

3.106

3.213

1.

These capacities are net capacities - the indoor motor heat has been added. These power inputs are total power inputs - the indoor motor watts have
been added.

TABLE 12: HEATING CAPACITIES - 3-1/2 TON (BHP042)

CFM

RETURN

AIR °F

CAP

1

& KW

OUTDOOR AIR TEMPERATURE, °F (72% RH)

-10

0

10

20

30

40

50

60

1050

55

MBH

15.404

17.988

20.968

24.404

28.369

32.941

38.215

44.298

KW

2.410

2.505

2.599

2.694

2.789

2.883

2.978

3.073

70

MBH

14.342

16.926

19.906

23.342

27.307

31.879

37.153

43.236

KW

2.835

2.930

3.024

3.119

3.214

3.308

3.403

3.498

80

MBH

13.669

16.253

19.233

22.669

26.634

31.206

36.480

42.563

KW

3.143

3.238

3.332

3.427

3.522

3.616

3.711

3.806

1400

55

MBH

17.901

20.485

23.465

26.901

30.866

35.438

40.712

46.795

KW

2.419

2.514

2.608

2.703

2.798

2.892

2.987

3.082

70

MBH

16.839

19.423

22.403

25.839

29.804

34.376

39.650

45.733

KW

2.844

2.939

3.033

3.128

3.223

3.317

3.412

3.507

80

MBH

16.166

18.750

21.730

25.166

29.131

33.703

38.977

45.060

KW

3.152

3.247

3.341

3.436

3.531

3.625

3.720

3.815

1750

55

MBH

18.901

21.485

24.465

27.901

31.866

36.438

41.712

47.795

KW

2.463

2.558

2.652

2.747

2.842

2.936

3.031

3.126

70

MBH

17.839

20.423

23.403

26.839

30.804

35.376

40.650

46.733

KW

2.888

2.983

3.077

3.172

3.267

3.361

3.456

3.551

80

MBH

17.166

19.750

22.730

26.166

30.131

34.703

39.977

46.060

KW

3.196

3.291

3.385

3.480

3.575

3.669

3.764

3.859

1.

These capacities are net capacities - the indoor motor heat has been added. These power inputs are total power inputs - the indoor motor watts have
been added.