Multipliers for determining the performance with other indoor sections.

NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.

NOTE: KW RATING IS FOR OUTDOOR AND INDOOR UNITS.

LOW CFM

COOLING PERFORMANCE DATA - LOW CFM 1-STAGE OPERATION

OUTDOOR UNIT MODEL NO. CZH04811

INDOOR COIL MODEL NO.

FC62D + MV20D

CONDENSER

ENTERING AIR

TEMPERATURE

ID CFM

950

1000

1050

ID DB (°F)

80

80

75

80

80

80

80

75

80

80

80

80

75

80

80

ID WB (°F)

57

62

62

67

72

57

62

62

67

72

57

62

62

67

72

65

T.C.

35.4 36.6 36.2 39.8 42.3 36.1 37.2 36.8 40.2 42.9 36.8 37.8 37.4 40.6 43.4

S.C.

34.3 31.8 26.9 27.2 21.7 34.8 32.5 27.6 27.8 22.0 35.3 33.3 28.2 28.5 22.3

K.W.

1.50 1.50 1.49 1.48 1.48 1.50 1.49 1.49 1.48 1.47 1.49 1.49 1.49 1.47 1.47

75

T.C.

34.0 34.9 34.5 37.8 40.4 34.6 35.4 35.0 38.2 40.9 35.2 36.0 35.5 38.6 41.5

S.C.

32.9 31.0 26.2 26.4 21.0 33.4 31.7 26.8 27.0 21.3 33.9 32.4 27.4 27.6 21.7

K.W.

1.81 1.81 1.81 1.80 1.79 1.81 1.81 1.80 1.79 1.78 1.80 1.80 1.80 1.79 1.78

85

T.C.

32.5 33.1 32.8 35.7 38.5 33.1 33.7 33.2 36.2 39.0 33.7 34.2 33.6 36.6 39.5

S.C.

31.5 30.2 25.5 25.5 20.3 32.0 30.9 26.0 26.1 20.7 32.5 31.6 26.6 26.7 21.1

K.W.

2.12 2.12 2.12 2.11 2.10 2.12 2.12 2.12 2.11 2.10 2.12 2.12 2.11 2.11 2.09

95

T.C.

31.1 31.4 31.1 33.7 36.6 31.7 31.9 31.4 34.2 37.1 32.2 32.4 31.7 34.6 37.6

S.C.

30.1 29.4 24.8 24.7 19.6 30.6 30.1 25.3 25.3 20.0 31.1 30.8 25.8 25.8 20.4

K.W.

2.44 2.44 2.44 2.43 2.41 2.43 2.43 2.43 2.43 2.41 2.43 2.43 2.43 2.42 2.40

105

T.C.

29.4 29.7 28.9 31.5 34.2 30.0 30.2 29.3 31.9 34.6 30.5 30.7 29.6 32.3 35.0

S.C.

28.5 27.8 23.8 23.8 18.7 28.9 28.5 24.3 24.4 19.1 29.4 29.1 24.8 24.9 19.6

K.W.

2.86 2.87 2.87 2.87 2.84 2.86 2.86 2.86 2.86 2.84 2.86 2.86 2.86 2.85 2.84

115

T.C.

27.8 28.0 26.9 29.3 31.9 28.4 28.6 27.2 29.7 32.2 28.9 29.1 27.6 30.1 32.5

S.C.

26.9 26.3 22.9 23.0 17.8 27.4 26.9 23.4 23.5 18.3 27.8 27.5 23.9 24.1 18.7

K.W.

3.28 3.28 3.29 3.29 3.26 3.27 3.28 3.28 3.27 3.26 3.27 3.27 3.28 3.27 3.26

125

T.C.

26.2 26.4 24.8 27.1 29.6 26.7 26.9 25.2 27.5 29.8 27.2 27.5 25.6 27.9 30.0

S.C.

25.4 24.8 21.9 22.1 16.9 25.8 25.4 22.4 22.7 17.4 26.2 26.0 22.9 23.3 17.9

K.W.

3.69 3.70 3.71 3.71 3.67 3.69 3.69 3.70 3.69 3.67 3.69 3.69 3.70 3.68 3.68

NOTE: ALL CAPACITIES ARE NET (KBTUH) WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.

Air Handler

Coil

T.C.

S.C.

KW

AV/SV48D

0.97 0.97 1.00

AV/SV60D

0.97 0.97 1.00

F4FV060

0.99 0.98 1.01

MV16C

FC/MC/PC48C

1.00 1.00 0.99

MV16C

FC/MC/PC48D

1.00 1.00 0.99

MV16C

UC48D

1.00 1.00 0.99

MV20D

FC/MC/PC48D

1.00 1.00 1.00

MV20D

UC48D

1.00 1.00 1.00

MV20D FC/MC62D 1.00

1.00

1.00

Variable Speed
Furnace

Coil

T.C.

S.C.

KW

PV8*C16

FC/MC/PC48C

0.97 0.97 0.98

PV8*C16

FC/MC/PC48D

0.97 0.97 0.98

PV8*C16

UC48D

0.97 0.97 0.98

PV8*C20

FC/MC/PC48C

1.00 1.00 0.99

PV8*C20

FC/MC/PC48D

1.00 1.00 0.99

PV8*C20

UC48D

1.00 1.00 0.99

P(C,V)9*C16

FC/MC/PC48C

1.01 1.02 0.98

P(C,V)9*C16

FC/MC/PC48D

1.01 1.02 0.98

P(C,V)9*C16

UC48D

1.01 1.02 0.98

P(C,V)9*C20

FC/MC/PC48C

0.99 0.99 1.00

P(C,V)9*C20

FC/MC/PC48D

0.99 0.99 1.00

P(C,V)9*C20

UC48D

0.99 0.99 1.00

P(C,V)9*D20

FC/MC/PC48D

0.99 0.99 1.00

P(C,V)9*D20

UC48D

0.99 0.99 1.00

PV8*C20

FC/MC62D

1.00 1.00 0.99

P(C,V)9*C20

FC/MC62D

1.00 1.00 1.00

P(C,V)9*D20

FC/MC62D

0.99 0.99 1.00

P(C,V)9*D20

HC60D

0.95 0.95 1.00