Multipliers for determining the performance with other indoor sections.

NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.

NOTE: KW RATING IS FOR OUTDOOR AND INDOOR UNITS.

LOW CFM

COOLING PERFORMANCE DATA - LOW CFM 1-STAGE OPERATION

OUTDOOR UNIT MODEL NO. CZH03611

INDOOR COIL MODEL NO.

FC62D + MV12D

CONDENSER

ENTERING AIR

TEMPERATURE

ID CFM

750

800

850

ID DB (°F)

80

80

75

80

80

80

80

75

80

80

80

80

75

80

80

ID WB (°F)

57

62

62

67

72

57

62

62

67

72

57

62

62

67

72

65

T.C.

25.4 26.8 27.2 29.7 32.8 25.9 27.0 27.3 30.1 33.0 26.4 27.2 27.5 30.4 33.2

S.C.

25.0 22.9 19.4 19.3 15.3 25.6 23.7 19.9 19.8 15.7 26.1 24.6 20.4 20.2 16.1

K.W.

1.00 0.99 0.99 0.96 0.93 0.99 0.98 0.98 0.95 0.92 0.97 0.97 0.97 0.94 0.91

75

T.C.

24.3 25.5 25.7 28.3 31.2 24.9 25.7 25.9 28.6 31.3 25.4 26.0 26.1 28.9 31.5

S.C.

24.0 22.3 18.8 18.7 14.8 24.6 23.1 19.4 19.2 15.3 25.1 23.8 19.9 19.7 15.7

K.W.

1.24 1.23 1.23 1.20 1.17 1.22 1.22 1.22 1.19 1.16 1.21 1.21 1.21 1.18 1.16

85

T.C.

23.3 24.2 24.3 26.9 29.5 23.8 24.5 24.5 27.2 29.7 24.3 24.7 24.8 27.5 29.8

S.C.

23.0 21.8 18.3 18.2 14.4 23.6 22.4 18.8 18.7 14.9 24.1 23.0 19.3 19.2 15.3

K.W.

1.47 1.47 1.47 1.44 1.41 1.46 1.46 1.46 1.43 1.41 1.45 1.45 1.45 1.42 1.40

95

T.C.

22.2 22.9 22.8 25.4 27.9 22.7 23.2 23.1 25.8 28.0 23.3 23.5 23.4 26.1 28.2

S.C.

22.0 21.2 17.7 17.6 14.0 22.6 21.7 18.2 18.2 14.5 23.1 22.2 18.8 18.7 14.9

K.W.

1.71 1.71 1.71 1.68 1.65 1.70 1.70 1.70 1.67 1.65 1.69 1.69 1.69 1.66 1.64

105

T.C.

20.8 21.3 21.0 23.6 26.0 21.3 21.7 21.3 23.8 26.1 21.9 22.1 21.5 24.1 26.2

S.C.

20.6 20.0 16.8 16.8 13.4 21.2 20.5 17.4 17.4 13.7 21.7 21.0 17.9 17.9 14.1

K.W.

2.03 2.03 2.03 2.01 1.98 2.02 2.02 2.02 2.00 1.97 2.00 2.01 2.01 1.99 1.97

115

T.C.

19.4 19.7 19.3 21.7 24.1 20.0 20.2 19.5 22.0 24.2 20.5 20.7 19.7 22.2 24.3

S.C.

19.2 18.8 16.0 16.1 12.8 19.8 19.3 16.6 16.6 13.0 20.4 19.8 17.1 17.1 13.3

K.W.

2.34 2.33 2.34 2.32 2.30 2.33 2.33 2.33 2.31 2.29 2.31 2.32 2.32 2.30 2.28

125

T.C.

18.0 18.2 17.5 19.9 22.2 18.6 18.8 17.7 20.1 22.3 19.1 19.3 18.0 20.4 22.4

S.C.

17.8 17.6 15.2 15.3 12.2 18.4 18.1 15.8 15.8 12.3 19.0 18.5 16.4 16.3 12.5

K.W.

2.65 2.64 2.65 2.63 2.62 2.64 2.64 2.65 2.63 2.61 2.62 2.63 2.64 2.62 2.60

NOTE: ALL CAPACITIES ARE NET (KBTUH) WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.

Air Handler

Coil

T.C.

S.C.

KW

AV36C

1.00 1.00 1.01

MV12B

FC/MC/PC43B

1.00 0.99 1.03

MV12B

FC/MC/PC43C

1.00 0.99 1.03

MV16C

FC/MC/PC43C

1.00 1.00 1.03

MV12D

FC/MC/PC48D

1.00 0.99 1.00

MV12D

UC48D

1.00 0.99 1.00

MV16C

FC/MC/PC48C

1.01 1.01 1.01

MV16C

FC/MC/PC48D

1.01 1.01 1.01

MV16C

UC48D

1.01 1.01 1.01

MV20D

FC/MC/PC48D

1.00 1.00 1.01

MV20D

UC48D

1.00 1.00 1.01

MV12D FC/MC62D 1.00

1.00

1.00

MV20D FC/MC62D 1.01

1.01

1.01

Variable Speed
Furnace

Coil

T.C.

S.C.

KW

PV8*A12

FC/MC/PC37A

0.99 0.99 1.03

PV9*A12

FC/MC/PC37A

1.00 0.99 1.04

PV8*B16

FC/MC/PC43B

0.99 0.99 1.02

PV8*B16

FC/MC/PC43C

0.99 0.99 1.02

PV8*C16

FC/MC/PC43C

0.96 0.96 1.00

PV8*C20

FC/MC/PC43C

1.00 1.00 1.02

P(C,V)9*B12

FC/MC/PC43B

1.00 0.99 1.03

P(C,V)9*B12

FC/MC/PC43C

1.00 0.99 1.03

P(C,V)9*C16

FC/MC/PC43C

1.00 1.00 1.01

P(C,V)9*C20

FC/MC/PC43C

1.00 1.00 1.03

PV8*C16

FC/MC/PC48C

0.96 0.96 0.98

PV8*C16

FC/MC/PC48D

0.96 0.96 0.98

PV8*C16

UC48D

0.96 0.96 0.98

PV8*C20

FC/MC/PC48C

1.01 1.01 1.00

PV8*C20

FC/MC/PC48D

1.01 1.01 1.00

PV8*C20

UC48D

1.01 1.01 1.00

P(C,V)9*C16

FC/MC/PC48C

1.01 1.01 0.99

P(C,V)9*C16

FC/MC/PC48D

1.01 1.01 0.99

P(C,V)9*C16

UC48D

1.01 1.01 0.99

P(C,V)9*C20

FC/MC/PC48C

1.01 1.01 1.02

P(C,V)9*C20

FC/MC/PC48D

1.01 1.01 1.02

P(C,V)9*C20

UC48D

1.01 1.01 1.02

P(C,V)9*D20

FC/MC/PC48D

1.01 1.01 1.01

P(C,V)9*D20

UC48D

1.01 1.01 1.01

PV8*C20

FC/MC62D

1.01 1.01 1.01

P(C,V)9*C20

FC/MC62D

1.01 1.01 1.02

P(C,V)9*D20

FC/MC62D

1.01 1.01 1.02

PV8*C16

HC42C

0.96 0.96 0.99

PV8*C20

HC42C

1.00 1.00 1.01

P(C,V)9*C16

HC42C

1.00 0.99 1.01

P(C,V)9*C20

HC42C

1.00 1.00 1.03

Variable Speed
Furnace

Coil

T.C.

S.C.

KW