Multipliers for determining the performance with other indoor sections.

NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree belowthe listed temperature.

COOLING PERFORMANCE DATA

AIR CONDITIONER MODEL NO.

H1RA024S78A

INDOOR COIL MODEL NO.

G2FD030S17

CONDENSER

ENTERING AIR

TEMPERATURE

IDCFM

650

850

1050

ID DB (°F)

85

80

70

85

80

70

85

80

70

ID WB (°F)

72

67

57

72

67

57

72

67

57

75

T.C.

26.4

25.3

24.0

26.6

25.7

24.6

26.7

26.1

25.2

S.C.

15.4

15.6

15.4

16.2

16.7

16.8

16.9

17.8

18.2

K.W

2.15

2.11

2.08

2.17

2.13

2.10

2.18

2.15

2.12

85

T.C.

25.4

23.9

21.8

25.7

24.6

22.8

26.1

25.2

23.7

S.C.

15.3

15.1

14.4

16.4

16.6

16.2

17.4

18.2

18.1

K.W

2.31

2.26

1.16

2.33

2.28

2.23

2.36

2.31

2.26

95

T.C.

24.4

22.5

19.6

24.9

23.4

20.9

25.4

24.3

22.2

S.C.

15.3

14.6

13.4

16.6

16.6

15.7

17.9

18.5

17.9

K.W

2.47

2.40

2.31

2.50

2.44

2.35

2.53

2.47

2.39

105

T.C.

22.5

20.1

17.6

23.2

21.1

18.6

23.9

22.1

19.6

S.C.

14.7

13.8

12.7

16.4

15.9

14.7

18.1

17.9

16.8

K.W

2.62

2.53

2.44

2.66

2.57

2.47

2.70

2.61

2.51

115

T.C.

20.6

17.7

15.6

21.5

18.8

16.3

22.4

19.8

16.9

S.C.

14.2

13.0

11.9

16.3

15.2

13.8

18.3

17.3

15.6

K.W

2.76

2.65

2.56

2.81

2.70

2.59

2.86

2.74

2.62

125

T.C.

17.8

15.2

13.3

18.7

15.9

14.0

19.5

16.7

14.7

S.C.

13.3

12.4

11.4

15.4

14.3

13.1

17.4

16.1

14.7

K.W

2.89

2.78

2.69

2.94

2.82

2.72

2.99

2.85

2.75

NOTE: ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.

Air Handler

Coil

T.C.

S.C.

KW

N1AHB1293

G2FD030S17 1.00

1.00

1.00

F2RP024N93

1.00

1.00

1.00