Cooling performance data – York 036-21103-003 User Manual

Page 12

background image

036-21103-003 Rev. A (0403)

12

Unitary Products Group

Multipliers for determining the performance with other indoor sections.

NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree belowthe listed temperature.

COOLING PERFORMANCE DATA

AIR CONDITIONER MODEL NO.

H1RA048S50A

INDOOR COIL MODEL NO.

G2FD048S21

CONDENSER

ENTERING AIR

TEMPERATURE

IDCFM

1400

1450

1500

ID DB (°F)

85

80

70

85

80

70

85

80

70

ID WB (°F)

72

67

57

72

67

57

72

67

57

75

T.C.

66.1

57.0

47.9

63.5

55.8

48.1

61.0

54.6

48.3

S.C.

34.2

34.3

34.3

34.7

35.1

35.6

35.1

36.0

36.8

K.W

4.49

4.83

4.70

4.99

5.09

4.96

4.98

4.84

4.70

85

T.C.

58.8

51.6

44.5

57.7

51.2

44.7

56.5

50.8

45.0

S.C.

33.2

33.1

32.9

33.9

34.0

34.1

34.6

34.9

35.2

K.W

4.93

5.03

4.80

5.60

5.57

5.42

5.50

5.34

5.18

95

T.C.

51.5

46.3

41.1

51.8

46.6

41.4

52.1

46.9

41.7

S.C.

32.1

31.9

31.6

33.1

32.9

32.6

34.1

33.8

33.6

K.W

5.36

5.22

5.08

5.67

5.51

5.35

5.47

5.29

5.11

105

T.C.

44.2

40.9

37.7

45.9

42.0

38.0

47.6

43.0

38.4

S.C.

31.1

30.7

30.2

32.4

31.7

31.1

33.6

32.8

32.0

K.W

5.82

5.67

5.53

6.16

5.99

5.81

5.99

5.79

5.59

115

T.C.

36.9

35.6

34.3

40.0

37.4

34.7

43.1

39.1

35.1

S.C.

30.1

29.5

28.9

31.6

30.6

29.6

33.1

31.7

30.3

K.W

5.76

5.61

5.46

6.12

5.93

5.75

5.96

5.74

5.52

125

T.C.

39.5

35.3

31.1

39.6

35.4

31.3

39.7

35.6

31.6

S.C.

28.2

27.9

27.5

27.1

28.8

30.5

25.9

29.7

33.6

K.W

6.11

5.93

5.75

6.43

6.23

6.03

6.23

6.01

5.79

NOTE: ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.

Air Handler

Coil

T.C.

S.C.

KW

NAHC1693

G2FD048S21

1.00

1.00

1.00

F2RP048N93

1.00

1.00

1.00