beautypg.com

Dimensions – York YCUL0016 User Manual

Page 62

background image

YORK INTERNATIONAL

62

YORK INTERNATIONAL

63

FORM 150.63-EG1

��������

����������������������������

�������������

��������

�����������������������

�����������������������

�����������

�����������

�����������

�������

������

������

������

������

������

������

��

���������

�����������

����������

������

�������

������������

Dimensions -

YCUL0016 - YCUL0026 (English)

NOTE:
Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reliable

operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable

airflow patterns and possible diminished performance. YORK’s unit controls will optimize operation without nuisance high-pressure

safety cutouts; however, the system designer must consider potential performance degradation. Access to the unit control center

assumes the unit is no higher than on spring isolators. Recommended minimum clearances: Side to wall – 6'; rear to wall – 6';

control panel to end wall – 4'0; top – no obstructions allowed; distance between adjacent units – 10'. No more than one adjacent

wall may be higher than the unit.

LD04417

MODEL YCUL

A

0016

22 5/16”

0026

22 3/16”

This manual is related to the following products: