Physical data, Si units) – York YCUL0016 User Manual
Page 60
YORK INTERNATIONAL
60
YORK INTERNATIONAL
61
FORM 150.63-EG1
Physical Data -
(SI Units)
Notes:
1. Pump Down Capacity is based on 100°F (37.8°C) liquid R22 and 80% of condenser volume.
2. Operating Refrigerant Charge is for Condensing Unit only, does not include refrigerant lines and evaporator coil.
Model Number YCUL
0016
0026
0030
0036
0040
0046
0050
0056
0060
General Unit Data
Nominal kW, R-22
53.5
73.2
91.1
109.7
132.6
148.8
164.9
181.8
197.7
Nominal kW, R-407C
51.0
70.7
88.3
108.0
128.7
143.8
160.0
176.6
193.1
Number of Refrigerant Circuits
1
1
1
1
1
2
2
2
2
Refrigerant Charge, Operating
R-22, ckt1 / ckt2, kg
11.7
13.3
18.7
23.4
24.2
16.4/16.4
19.5/16.4
19.5/19.5
28.9/19.5
R-407C, ckt1 / ckt2, kg
11.3
12.8
18.0
22.6
23.3
15.8/15.8
18.8/15.8
18.8/18.8
27.9/18.8
Pumpdown Capacity
R-22, ckt1 / ckt2, lbs
19.6
19.6
27.4
41.1
41.1
26.5/26.5
26.5/26.5
26.5/26.5
26.5/26.5
R-407C, ckt1 / ckt2, lbs
18.9
18.9
26.4
39.6
39.6
25.5/25.5
25.5/25.5
25.5/25.5
25.5/25.5
Oil Charge, ckt1 / ckt2, liters
8.3
8.3
8.3
8.3
12.5
8.3/8.3
8.3/8.3
8.3/8.3
8.3/8.3
Shipping Weight
Aluminum Fin Coils, kg
930
934
1089
1109
1265
1790
1814
1840
1866
Copper Fin Coils, kg
998
1002
1157
1177
1333
1926
1950
1976
2002
Compressors, scroll type
Compressors per circuit
2
2
2
2
3
2
2
2
2
Compressors per unit
2
2
2
2
3
4
4
4
4
Nominal kWo per compressor
26
35
46
53
46
35/35
46/35
46/46
53/46
Condenser
Total Face Area meters
2
4
4
6
6
6
12
12
12
12
Number of Rows
2
2
2
3
3
2
2
2
2
Fins per m
512
512
512
512
512
512
512
512
512
Condenser Fans
Number of Fans total
2
2
2
2
2
4
4
4
4
Fan hp/kw
2 / 1.4
2 / 1.4
2 / 1.4
2 / 1.4
2 / 1.4
2 / 1.4
2 / 1.4
2 / 1.4
2 / 1.4
Fan RPM
1140
1140
1140
1140
1140
1140
1140
1140
1140
Number of Blades
3
3
3
3
3
3
3
3
3
Total Chiller Airflow l/s
7672
7672
11091
11091
11091
22351
22351
22351
22351