Electrical data, Voltage range – York YCUL0016 User Manual
Page 103
YORK INTERNATIONAL
102
YORK INTERNATIONAL
103
FORM 150.63-EG1
YCUL0016 - YCUL0040
SINGLE POINT POWER SUPPLY CONNECTIONS (See Fig. 1)
(One Field Provided Power Supply to the condensing unit. Field connections to Factory Provided Power Terminal Block (standard), Non-Fused Disconnect Switch
(optional) or Circuit Breaker (optional).)
OVER CURRENT PROTECTION,
UNIT VOLTAGE UNIT VOLTAGE CONTROL POWER MCA SEE NOTE B NFDISC Sw
NOTE A MIN MAX
MODELS w/o
CONTROL TRANS 115-1-60/50 15A 10A 15A 30 A / 240V
-17 200-1-60 15A 10A 15A 30 A / 240V
-28 230-1-60 15A 10A 15A 30 A / 240V
MODELS w/
-40 380-1-60 15A 10A 15A 30 A / 480V
CONTROL TRANS
-46 460-1-60 15A 10A 15A 30 A / 480V
-58 575-1-60 15A 10A 15A 30 A / 600V
Electrical Data
SINGLE POINT FIELD SUPPLIED WIRING
SYSTEM #1 COMPRESSOR & FAN
MODEL
YCUL VOLT HZ MCA
1
MIN
N/F
DISC
SW
2
D.E. FUSE CKT. BKR.
5
INCOMING (LUGS) WIRE RANGE
6
COMPR. #1 COMPR. #2 COMPR. #3
FANS
TERMINAL
BLOCK (std)
NF DISC.
SWITCH
(opt)
CIRCUIT
BREAKER
(opt)
MIN
3
MAX
4
MIN MAX
RLA LRA RLA LRA RLA LRA QTY FLA
(EA)
0016
200
60
71
100
80
90
80
90
# 10 - # 1
# 14 - 1/0
# 14 - 1/0 24.0 189 24.0
189
—
—
2
8.2
230
60
70
100
80
90
80
90
# 10 - # 1
# 14 - 1/0
# 14 - 1/0 24.0 189 24.0
189
—
—
2
7.8
380
60
42
60
50
50
50
50
# 10 - # 1
# 14 - 2
# 14 - 2
14.4 112 14.4
112
—
—
2
4.8
460
60
35
60
40
45
40
45
# 10 - # 1
# 14 - 2
# 14 - 2
12.0 99
12.0
99
—
—
2
4.0
575
60
28
30
35
35
35
35
# 10 - # 1
# 14 - 2
# 14 - 2
9.6
74
9.6
74
—
—
2
3.1
0026
200
60
92
100
100 110
100
110
# 10 - # 1
# 14 - 1/0
# 14 - 1/0 33.2 278 33.2
278
—
—
2
8.2
230
60
91
100
100 110
100
110
# 10 - # 1
# 14 - 1/0
# 14 - 1/0 33.2 278 33.2
278
—
—
2
7.8
380
60
55
60
60
70
60
70
# 10 - # 1
# 14 - 2
# 14 - 2
19.9 151 19.9
151
—
—
2
4.8
460
60
46
60
50
60
50
60
# 10 - # 1
# 14 - 2
# 14 - 2
16.6 127 16.6
127
—
—
2
4.0
575
60
37
60
40
45
40
45
# 10 - # 1
# 14 - 2
# 14 - 2
13.3 100 13.3
100
—
—
2
3.1
0030
200
60 107
150
125 125
125
125
# 10 - # 1
# 2 - 4/0
# 2 - 4/0
40.0 350 40.0
350
—
—
2
8.2
230
60 106
150
125 125
125
125
# 10 - # 1
# 2 - 4/0
# 2 - 4/0
40.0 350 40.0
350
—
—
2
7.8
380
60
64
100
70
80
70
80
# 10 - # 1
# 14 - 1/0
# 14 - 1/0 24.0 195 24.0
195
—
—
2
4.8
460
60
53
60
60
70
60
70
# 10 - # 1
# 14 - 2
# 14 - 2
19.9 167 19.9
167
—
—
2
4.0
575
60
43
60
50
50
50
50
# 10 - # 1
# 14 - 2
# 14 - 2
16.0 125 16.0
125
—
—
2
3.1
0036
200
60 124
150
150 150
150
150
# 10 - 3/0
# 2 - 4/0
# 2 - 4/0
47.8 425 47.8
425
—
—
2
8.2
230
60 124
150
150 150
150
150
# 10 - 3/0
# 2 - 4/0
# 2 - 4/0
47.8 425 47.8
425
—
—
2
7.8
380
60
75
100
90
90
90
90
# 10 - # 1
# 14 - 1/0
# 14 - 1/0 28.7 239 28.7
239
—
—-
2
4.8
460
60
62
100
70
70
70
70
# 10 - # 1
# 14 - 1/0
# 14 - 1/0 23.9 198 23.9
198
—
—
2
4.0
575
60
50
60
60
60
60
60
# 10 - # 1
# 14 - 2
# 14 - 2
19.1 148 19.1
148
—
—
2
3.1
0040
200
60 147
200
175 175
175
175
# 10 - 3/0
# 3 - 300
# 3 - 300
40.0 350 40.0
350 40.0 350
2
8.2
230
60 146
200
175 175
175
175
# 10 - 3/0
# 3 - 300
# 3 - 300
40.0 350 40.0
350 40.0 350
2
7.8
380
60
88
100
100 110
100
110
# 10 - # 1
# 14 - 1/0
# 14 - 1/0 24.0 195 24.0
195 24.0 195
2
4.8
460
60
73
100
80
90
80
90
# 10 - # 1
# 14 - 1/0
# 14 - 1/0 19.9 167 19.9
167 19.9 167
2
4.0
575
60
59
100
70
70
70
70
# 10 - # 1
# 14 - 1/0
# 14 - 1/0 16.0 125 16.0
125 16.0 125
2
3.1
VOLTAGE RANGE
VOLTAGE CODE
UNIT POWER
MIN.
MAX.
-17
200-3-60
180
220
-28
230-3-60
207
253
-40
380/415-3-60
342
440
-46
460-3-60
414
506
-58
575-3-60
517
633
A. Minimum #14 AWG, 75°C, Copper Recommended
B. Minimum and Maximum Over Current Protection, Dual Element Fuse or Circuit Breaker