beautypg.com

Electrical data, Voltage range – York YCUL0016 User Manual

Page 103

background image

YORK INTERNATIONAL

102

YORK INTERNATIONAL

103

FORM 150.63-EG1

YCUL0016 - YCUL0040

SINGLE POINT POWER SUPPLY CONNECTIONS (See Fig. 1)

(One Field Provided Power Supply to the condensing unit. Field connections to Factory Provided Power Terminal Block (standard), Non-Fused Disconnect Switch

(optional) or Circuit Breaker (optional).)

OVER CURRENT PROTECTION,
UNIT VOLTAGE UNIT VOLTAGE CONTROL POWER MCA SEE NOTE B NFDISC Sw
NOTE A MIN MAX

MODELS w/o
CONTROL TRANS
115-1-60/50 15A 10A 15A 30 A / 240V

-17 200-1-60 15A 10A 15A 30 A / 240V
-28 230-1-60 15A 10A 15A 30 A / 240V

MODELS w/

-40 380-1-60 15A 10A 15A 30 A / 480V

CONTROL TRANS

-46 460-1-60 15A 10A 15A 30 A / 480V

-58 575-1-60 15A 10A 15A 30 A / 600V

Electrical Data

SINGLE POINT FIELD SUPPLIED WIRING

SYSTEM #1 COMPRESSOR & FAN

MODEL

YCUL VOLT HZ MCA

1

MIN

N/F

DISC

SW

2

D.E. FUSE CKT. BKR.

5

INCOMING (LUGS) WIRE RANGE

6

COMPR. #1 COMPR. #2 COMPR. #3

FANS

TERMINAL

BLOCK (std)

NF DISC.

SWITCH

(opt)

CIRCUIT

BREAKER

(opt)

MIN

3

MAX

4

MIN MAX

RLA LRA RLA LRA RLA LRA QTY FLA

(EA)

0016

200

60

71

100

80

90

80

90

# 10 - # 1

# 14 - 1/0

# 14 - 1/0 24.0 189 24.0

189

2

8.2

230

60

70

100

80

90

80

90

# 10 - # 1

# 14 - 1/0

# 14 - 1/0 24.0 189 24.0

189

2

7.8

380

60

42

60

50

50

50

50

# 10 - # 1

# 14 - 2

# 14 - 2

14.4 112 14.4

112

2

4.8

460

60

35

60

40

45

40

45

# 10 - # 1

# 14 - 2

# 14 - 2

12.0 99

12.0

99

2

4.0

575

60

28

30

35

35

35

35

# 10 - # 1

# 14 - 2

# 14 - 2

9.6

74

9.6

74

2

3.1

0026

200

60

92

100

100 110

100

110

# 10 - # 1

# 14 - 1/0

# 14 - 1/0 33.2 278 33.2

278

2

8.2

230

60

91

100

100 110

100

110

# 10 - # 1

# 14 - 1/0

# 14 - 1/0 33.2 278 33.2

278

2

7.8

380

60

55

60

60

70

60

70

# 10 - # 1

# 14 - 2

# 14 - 2

19.9 151 19.9

151

2

4.8

460

60

46

60

50

60

50

60

# 10 - # 1

# 14 - 2

# 14 - 2

16.6 127 16.6

127

2

4.0

575

60

37

60

40

45

40

45

# 10 - # 1

# 14 - 2

# 14 - 2

13.3 100 13.3

100

2

3.1

0030

200

60 107

150

125 125

125

125

# 10 - # 1

# 2 - 4/0

# 2 - 4/0

40.0 350 40.0

350

2

8.2

230

60 106

150

125 125

125

125

# 10 - # 1

# 2 - 4/0

# 2 - 4/0

40.0 350 40.0

350

2

7.8

380

60

64

100

70

80

70

80

# 10 - # 1

# 14 - 1/0

# 14 - 1/0 24.0 195 24.0

195

2

4.8

460

60

53

60

60

70

60

70

# 10 - # 1

# 14 - 2

# 14 - 2

19.9 167 19.9

167

2

4.0

575

60

43

60

50

50

50

50

# 10 - # 1

# 14 - 2

# 14 - 2

16.0 125 16.0

125

2

3.1

0036

200

60 124

150

150 150

150

150

# 10 - 3/0

# 2 - 4/0

# 2 - 4/0

47.8 425 47.8

425

2

8.2

230

60 124

150

150 150

150

150

# 10 - 3/0

# 2 - 4/0

# 2 - 4/0

47.8 425 47.8

425

2

7.8

380

60

75

100

90

90

90

90

# 10 - # 1

# 14 - 1/0

# 14 - 1/0 28.7 239 28.7

239

—-

2

4.8

460

60

62

100

70

70

70

70

# 10 - # 1

# 14 - 1/0

# 14 - 1/0 23.9 198 23.9

198

2

4.0

575

60

50

60

60

60

60

60

# 10 - # 1

# 14 - 2

# 14 - 2

19.1 148 19.1

148

2

3.1

0040

200

60 147

200

175 175

175

175

# 10 - 3/0

# 3 - 300

# 3 - 300

40.0 350 40.0

350 40.0 350

2

8.2

230

60 146

200

175 175

175

175

# 10 - 3/0

# 3 - 300

# 3 - 300

40.0 350 40.0

350 40.0 350

2

7.8

380

60

88

100

100 110

100

110

# 10 - # 1

# 14 - 1/0

# 14 - 1/0 24.0 195 24.0

195 24.0 195

2

4.8

460

60

73

100

80

90

80

90

# 10 - # 1

# 14 - 1/0

# 14 - 1/0 19.9 167 19.9

167 19.9 167

2

4.0

575

60

59

100

70

70

70

70

# 10 - # 1

# 14 - 1/0

# 14 - 1/0 16.0 125 16.0

125 16.0 125

2

3.1

VOLTAGE RANGE

VOLTAGE CODE

UNIT POWER

MIN.

MAX.

-17

200-3-60

180

220

-28

230-3-60

207

253

-40

380/415-3-60

342

440

-46

460-3-60

414

506

-58

575-3-60

517

633

A. Minimum #14 AWG, 75°C, Copper Recommended
B. Minimum and Maximum Over Current Protection, Dual Element Fuse or Circuit Breaker

This manual is related to the following products: