Electrical data – York YCUL0016 User Manual
Page 108

YORK INTERNATIONAL
108
YORK INTERNATIONAL
109
FORM 150.63-EG1
Electrical Data
MODEL
YCUL
VOLT
HZ
SYSTEM #1 FIELD SUPPLIED WIRING
MCA
1
MIN N/F
DISC SW
2
D.E. FUSE
CKT. BKR.
5
INCOMING (LUGS) WIRE RANGE
6
MIN
3
MAX
4
MIN
MAX
TERMINAL BLOCK
(std)
NF DISC. SWITCHES
(opt)
CIR BREAKERS
(opt)
0096
200
60
251
400
300
350
300
350
# 6 - 400
(1 or 2) 3/0 - 500
(1 or 2) 3/0 - 500
230
60
233
250
300
300
300
300
# 6 - 400
(1) # 6 - 350
(1 or 2) 3/0 - 500
380
60
135
150
150
175
150
175
# 14 - 2/0
(1) # 6 - 350
(1) # 6 - 350
460
60
111
150
125
150
125
150
# 14 - 2/0
(1) # 6 - 350
(1) # 3 - 3/0
575
60
89
100
100
110
100
110
# 14 - 2/0
(1) # 6 - 350
(1) # 10 - 1/0
0100
200
60
251
400
300
350
300
350
# 6 - 400
(1 or 2) 3/0 - 500
(1 or 2) 3/0 - 500
230
60
233
250
300
300
300
300
# 6 - 400
(1) # 6 - 350
(1 or 2) 3/0 - 500
380
60
135
150
150
175
150
175
# 14 - 2/0
(1) # 6 - 350
(1) # 6 - 350
460
60
111
150
125
150
125
150
# 14 - 2/0
(1) # 6 - 350
(1) # 3 - 3/0
575
60
89
100
100
110
100
110
# 14 - 2/0
(1) # 6 - 350
(1) # 10 - 1/0
0106
200
60
274
400
300
300
300
300
(2) # 4 - 500
(1 or 2) 3/0 - 500
(1 or 2) 3/0 - 500
230
60
254
400
300
300
300
300
(2) # 4 - 500
(1 or 2) 3/0 - 500
(1 or 2) 3/0 - 500
380
60
148
200
175
175
175
175
# 14 - 2/0
(1) # 6 - 350
(1) # 3 - 3/0
460
60
122
150
150
150
150
150
# 14 - 2/0
(1) # 6 - 350
(1) # 10 - 1/0
575
60
98
150
110
110
110
110
# 14 - 2/0
(1) # 10 - 1/0
(1) # 10 - 1/0
0120
200
60
274
400
300
300
300
300
(2) # 4 - 500
(1 or 2) 3/0 - 500
(1 or 2) 3/0 - 500
230
60
254
400
300
300
300
300
(2) # 4 - 500
(1 or 2) 3/0 - 500
(1 or 2) 3/0 - 500
380
60
148
200
175
175
175
175
# 14 - 2/0
(1) # 6 - 350
(1) # 6 - 350
460
60
122
150
150
150
150
150
# 14 - 2/0
(1) # 6 - 350
(1) # 6 - 350
575
60
98
150
110
110
110
110
# 14 - 2/0
(1) # 6 - 350
(1) # 3 - 3/0
0130
200
60
359
400
400
450
400
450
(2) # 4 - 500
(1 or 2) 3/0 - 500
(1 or 2) 3/0 - 500
230
60
333
400
400
400
400
400
(2) # 4 - 500
(1 or 2) 3/0 - 500
(1 or 2) 3/0 - 500
380
60
194
250
225
225
225
225
# 6 - 400
(1) # 6 - 350
(1) # 6 - 350
460
60
159
200
175
200
175
200
# 6 - 400
(1) # 6 - 350
(1) # 6 - 350
575
60
128
150
150
150
150
150
# 14 - 2/0
(1) # 6 - 350
(1) # 6 - 350
MODEL
YCUL
VOLT
HZ
SYSTEM #2 FIELD SUPPLIED WIRING
MCA
1
MIN N/F
DISC SW
2
D.E. FUSE
CKT. BKR.
5
INCOMING (LUGS) WIRE RANGE
6
MIN
3
MAX
4
MIN
MAX
TERMINAL BLOCK
(std)
NF DISC. SWITCHES
(opt)
CIR BREAKERS
(opt)
0096
200
60
191
200
225
250
225
250
# 6 - 400
(1) # 6 - 350
(1) # 6 - 350
230
60
178
200
200
225
200
225
# 6 - 400
(1) # 6 - 350
(1) # 6 - 350
380
60
104
150
125
125
125
125
# 14 - 2/0
(1) # 6 - 350
(1) # 3 - 3/0
460
60
85
100
100
110
100
110
# 14 - 2/0
(1) # 10 - 1/0
(1) # 10 - 1/0
575
60
68
100
80
90
80
90
# 14 - 2/0
(1) # 10 - 1/0
(1) # 10 - 1/0
0100
200
60
251
400
300
350
300
350
# 6 - 400
(1 or 2) 3/0 - 500
(1 or 2) 3/0 - 500
230
60
233
250
300
300
300
300
# 6 - 400
(1) # 6 - 350
(1 or 2) 3/0 - 500
380
60
135
150
150
175
150
175
# 14 - 2/0
(1) # 6 - 350
(1) # 6 - 350
460
60
111
150
125
150
125
150
# 14 - 2/0
(1) # 6 - 350
(1) # 3 - 3/0
575
60
89
100
100
110
100
110
# 14 - 2/0
(1) # 6 - 350
(1) # 10 - 1/0
0106
200
60
259
400
300
350
300
350
# 6 - 400
(1 or 2) 3/0 - 500
(1 or 2) 3/0 - 500
230
60
241
250
300
300
300
300
# 6 - 400
(1) # 6 - 350
(1 or 2) 3/0 - 500
380
60
140
150
175
175
175
175
# 14 - 2/0
(1) # 6 - 350
(1) # 6 - 350
460
60
115
150
150
150
150
150
# 14 - 2/0
(1) # 6 - 350
(1) # 6 - 350
575
60
92
100
110
125
110
125
# 14 - 2/0
(1) # 6 - 350
(1) # 3 - 3/0
0120
200
60
274
400
300
300
300
300
(2) # 4 - 500
(1 or 2) 3/0 - 500
(1 or 2) 3/0 - 500
230
60
254
400
300
300
300
300
(2) # 4 - 500
(1 or 2) 3/0 - 500
(1 or 2) 3/0 - 500
380
60
148
200
175
175
175
175
# 14 - 2/0
(1) # 6 - 350
(1) # 6 - 350
460
60
122
150
150
150
150
150
# 14 - 2/0
(1) # 6 - 350
(1) # 6 - 350
575
60
98
150
110
110
110
110
# 14 - 2/0
(1) # 6 - 350
(1) # 3 - 3/0
0130
200
60
374
400
300
300
300
300
(2) # 4 - 500
(1 or 2) 3/0 - 500
(1 or 2) 3/0 - 500
230
60
354
400
300
300
300
300
(2) # 4 - 500
(1 or 2) 3/0 - 500
(1 or 2) 3/0 - 500
380
60
148
200
175
175
175
175
# 14 - 2/0
(1) # 6 - 350
(1) # 6 - 350
460
60
122
150
150
150
150
150
# 14 - 2/0
(1) # 6 - 350
(1) # 6 - 350
575
60
98
150
110
110
110
110
# 14 - 2/0
(1) # 6 - 350
(1) # 3 - 3/0
YCUL0096 - YCUL0130
MULTIPLE POINT POWER SUPPLY CONNECTIONS (see Fig. 3)
(Two Field Provided Power Supply Circuits to the condensing unit. Field connections to Factory Provided Terminal Blocks (standard), Non-Fused Disconnect
Switches (optional) or Individual System Circuit Breakers (optional) per electrical system.)
See Notes on page 100