Electrical data – York YCUL0016 User Manual
Page 104
YORK INTERNATIONAL
104
YORK INTERNATIONAL
105
FORM 150.63-EG1
MODEL
YCUL
VOLT HZ
SYSTEM #1 FIELD SUPPLIED WIRING
SYSTEM #1 COMPRESSOR & FAN
MCA
1
MIN N/F
DISC
SW
2
D.E. FUSE
CKT. BKR.
5
INCOMING
(LUGS) WIRE
RANGE
6
COMPR. #1
COMPR. #2
COMPR. #3
FANS
MIN
3
MAX
4
MIN
MAX
RLA
LRA
RLA
LRA
RLA
LRA QTY FLA (EA)
0046
200
60
92
100
100
110
100
110
# 10 - # 1
33.2
278
33.2
278
—
—
2
8.2
230
60
91
100
100
110
100
110
# 10 - # 1
33.2
278
33.2
278
—
—
2
7.8
380
60
55
60
60
70
60
70
# 10 - # 1
19.9
151
19.9
151
—
—
2
4.8
460
60
46
60
50
60
50
60
# 10 - # 1
16.6
127
16.6
127
—
—
2
4.0
575
60
37
60
40
45
40
45
# 10 - # 1
13.3
100
13.3
100
—
—
2
3.1
0050
200
60
107
150
125
125
125
125
# 10 - # 1
40.0
350
40.0
350
—
—
2
8.2
230
60
106
150
125
125
125
125
# 10 - # 1
40.0
350
40.0
350
—
—
2
7.8
380
60
64
100
70
90
70
90
# 10 - # 1
24.0
195
24.0
195
—
—
2
4.8
460
60
53
60
60
70
60
70
# 10 - # 1
19.9
167
19.9
167
—
—
2
4.0
575
60
43
60
50
50
50
50
# 10 - # 1
16.0
125
16.0
125
—
—
2
3.1
0056
200
60
107
150
125
125
125
125
# 10 - # 1
40.0
350
40.0
350
—
—
2
8.2
230
60
106
150
125
125
125
125
# 10 - # 1
40.0
350
40.0
350
—
—
2
7.8
380
60
64
100
70
80
70
80
# 10 - # 1
24.0
195
24.0
195
—
—
2
4.8
460
60
53
60
60
70
60
70
# 10 - # 1
19.9
167
19.9
167
—
—
2
4.0
575
60
43
60
50
50
50
50
# 10 - # 1
16.0
125
16.0
125
—
—
2
3.1
0060
200
60
124
150
150
150
150
150
# 10 - 3/0
47.8
425
47.8
425
—
—
2
8.2
230
60
124
150
150
150
150
150
# 10 - 3/0
47.8
425
47.8
425
—
—
2
7.8
380
60
75
100
90
100
90
100
# 10 - # 1
28.7
239
28.7
239
—
—
2
4.8
460
60
62
100
70
80
70
80
# 10 - # 1
23.9
198
23.9
198
—
—
2
4.0
575
60
50
60
60
60
60
60
# 10 - # 1
19.1
148
19.1
148
—
—
2
3.1
0066
200
60
124
150
150
150
150
150
# 10 - 3/0
47.8
425
47.8
425
—
—
2
8.2
230
60
124
150
150
150
150
150
# 10 - 3/0
47.8
425
47.8
425
—
—
2
7.8
380
60
75
100
90
100
90
100
# 10 - # 1
28.7
239
28.7
239
—
—
2
4.8
460
60
62
100
70
80
70
80
# 10 - # 1
23.9
198
23.9
198
—
—
2
4.0
575
60
50
60
60
60
60
60
# 10 - # 1
19.1
148
19.1
148
—-
—
2
3.1
0076
200
60
147
200
175
175
175
175
# 10 - 3/0
40.0
350
40.0
350
40.0
350
2
8.2
230
60
146
200
175
175
175
175
# 10 - 3/0
40.0
350
40.0
350
40.0
350
2
7.8
380
60
88
100
100
110
100
110
# 10 - # 1
24.0
195
24.0
195
24.0
195
2
4.8
460
60
73
100
80
90
80
90
# 10 - # 1
19.9
167
19.9
167
19.9
167
2
4.0
575
60
59
100
70
70
70
70
# 10 - # 1
16.0
125
16.0
125
16.0
125
2
3.1
0080
200
60
147
200
175
175
175
175
# 10 - 3/0
40.0
350
40.0
350
40.0
350
2
8.2
230
60
146
200
175
175
175
175
# 10 - 3/0
40.0
350
40.0
350
40.0
350
2
7.8
380
60
88
100
100
110
100
110
# 10 - # 1
24.0
195
24.0
195
24.0
195
2
4.8
460
60
73
100
80
90
80
90
# 10 - # 1
19.9
167
19.9
167
19.9
167
2
4.0
575
60
59
100
70
70
70
70
# 10 - # 1
16.0
125
16.0
125
16.0
125
2
3.1
0086
200
60
172
200
200
200
200
200
# 10 - 3/0
47.8
425
47.8
425
47.8
425
2
8.2
230
60
171
200
200
200
200
200
# 10 - 3/0
47.8
425
47.8
425
47.8
425
2
7.8
380
60
103
150
125
125
125
125
# 10 - # 1
28.7
239
28.7
239
28.7
239
2
4.8
460
60
86
100
100
100
100
100
# 10 - # 1
23.9
198
23.9
198
23.9
198
2
4.0
575
60
69
100
80
80
80
80
# 10 - # 1
19.1
148
19.1
148
19.1
148
2
3.1
0090
200
60
172
200
200
200
200
200
# 10 - 3/0
47.8
425
47.8
425
47.8
425
2
8.2
230
60
171
200
200
200
200
200
# 10 - 3/0
47.8
425
47.8
425
47.8
425
2
7.8
380
60
103
150
125
125
125
125
# 10 - # 1
28.7
239
28.7
239
28.7
239
2
4.8
460
60
86
100
100
100
100
100
# 10 - # 1
23.9
198
23.9
198
23.9
198
2
4.0
575
60
69
100
80
80
80
80
# 10 - # 1
19.1
148
19.1
148
19.1
148
2
3.1
See Notes on page 100
YCUL0046 - YCUL0090
DUAL POINT POWER SUPPLY CONNECTIONS (see Fig. 2)
(Two Field Provided Power Supply Circuits to the condensing unit. Field connections to Factory Provided Terminal Blocks per system.)
Electrical Data