Ratings, R22 (english units), Ycul0060ec – York YCUL0016 User Manual
Page 22: Ycul0066ec, Ycul0076ec, Ycul0080ec
YORK INTERNATIONAL
22
YORK INTERNATIONAL
23
FORM 150.63-EG1
Ratings -
R22 (English Units)
NOTES:
1. SST = Saturated Suction Temperature
2. kW = Compressors Input Power
3. EER = Condensing Unit EER (includes power from compressors, fans and the control panel)
YCUL0060EC
AIR TEMPERATURE ON CONDENSER (°F)
SST
(°F)
75°F
80°F
85°F
90°F
95°F
100°F
TONS
KW
EER TONS
KW
EER TONS
KW
EER TONS
KW
EER TONS
KW
EER TONS
KW
EER
35.0
52.2
45.7
12.2
51.0
48.2
11.4
49.7
50.9
10.6
48.5
53.8
9.8
47.1
56.8
9.1
45.8
60.0
8.4
37.0
54.1
46.1
12.6
52.9
48.6
11.7
51.6
51.3
10.9
50.3
54.2
10.1
48.9
57.3
9.3
47.5
60.5
8.6
39.0
56.1
46.5
12.9
54.8
49.1
12.0
53.4
51.8
11.2
52.1
54.7
10.4
50.7
57.7
9.6
49.2
61.0
8.9
41.0
58.1
47.0
13.3
56.7
49.5
12.4
55.4
52.2
11.5
53.9
55.1
10.7
52.5
58.2
9.9
51.0
61.5
9.1
43.0
60.1
47.4
13.6
58.7
50.0
12.7
57.3
52.7
11.8
55.8
55.6
11.0
54.3
58.7
10.1
52.8
62.0
9.4
45.0
62.2
47.9
13.9
60.8
50.4
13.0
59.3
53.2
12.1
57.8
56.1
11.2
56.2
59.2
10.4
54.7
62.5
9.6
47.0
64.3
48.4
14.3
62.8
50.9
13.3
61.3
53.6
12.4
59.8
56.6
11.5
58.2
59.7
10.7
56.5
63.0
9.9
49.0
66.5
48.9
14.6
65.0
51.4
13.7
63.4
54.2
12.7
61.8
57.1
11.8
60.1
60.2
11.0
58.5
63.5
10.1
51.0
68.7
49.5
15.0
67.1
52.0
14.0
65.5
54.7
13.0
63.8
57.6
12.1
62.2
60.8
11.2
60.4
64.1
10.4
53.0
70.9
50.0
15.3
69.3
52.5
14.3
67.6
55.2
13.3
65.9
58.2
12.4
64.2
61.3
11.5
62.4
64.7
10.7
55.0
73.2
50.6
15.6
71.5
53.1
14.6
69.8
55.8
13.6
68.1
58.8
12.7
66.3
61.9
11.8
64.4
65.3
10.9
YCUL0066EC
AIR TEMPERATURE ON CONDENSER (°F)
SST
(°F)
75°F
80°F
85°F
90°F
95°F
100°F
TONS
KW
EER TONS
KW
EER TONS
KW
EER TONS
KW
EER TONS
KW
EER TONS
KW
EER
35.0
57.6
47.7
13.0
56.2
50.4
12.1
54.9
53.3
11.2
53.5
56.3
10.4
52.1
59.6
9.6
50.6
63.0
8.9
37.0
59.7
48.1
13.3
58.3
50.8
12.4
56.9
53.7
11.5
55.5
56.8
10.7
54.0
60.1
9.9
52.5
63.5
9.1
39.0
61.8
48.6
13.7
60.4
51.3
12.7
59.0
54.2
11.8
57.5
57.3
11.0
56.0
60.6
10.2
54.4
64.0
9.4
41.0
64.0
49.0
14.1
62.6
51.7
13.1
61.1
54.7
12.2
59.6
57.8
11.3
58.0
61.1
10.4
56.4
64.5
9.7
43.0
66.2
49.5
14.4
64.7
52.2
13.4
63.2
55.1
12.5
61.7
58.3
11.6
60.1
61.6
10.7
58.4
65.1
9.9
45.0
68.5
50.0
14.8
67.0
52.7
13.8
65.4
55.7
12.8
63.8
58.8
11.9
62.2
62.1
11.0
60.5
65.6
10.2
47.0
70.8
50.6
15.1
69.2
53.3
14.1
67.7
56.2
13.1
66.0
59.3
12.2
64.3
62.6
11.3
62.6
66.2
10.5
49.0
73.2
51.1
15.5
71.6
53.8
14.5
69.9
56.7
13.5
68.2
59.9
12.5
66.5
63.2
11.6
64.7
66.8
10.7
51.0
75.6
51.7
15.8
73.9
54.4
14.8
72.2
57.3
13.8
70.5
60.5
12.8
68.7
63.8
11.9
66.9
67.4
11.0
53.0
78.0
52.3
16.2
76.3
55.0
15.1
74.6
57.9
14.1
72.8
61.1
13.1
71.0
64.4
12.2
69.1
68.0
11.3
55.0
80.5
52.9
16.5
78.7
55.6
15.4
77.0
58.6
14.4
75.2
61.7
13.4
73.3
65.1
12.4
71.3
68.6
11.5
YCUL0076EC
AIR TEMPERATURE ON CONDENSER (°F)
SST
(°F)
75°F
80°F
85°F
90°F
95°F
100°F
TONS
KW
EER TONS
KW
EER TONS
KW
EER TONS
KW
EER TONS
KW
EER TONS
KW
EER
35.0
64.2
55.4
12.4
62.6
58.6
11.5
61.0
61.9
10.7
59.4
65.5
9.9
57.7
69.2
9.1
55.9
73.1
8.4
37.0
66.6
55.9
12.7
64.9
59.0
11.8
63.3
62.4
11.0
61.6
65.9
10.2
59.8
69.7
9.4
58.0
73.7
8.6
39.0
69.0
56.3
13.1
67.3
59.5
12.2
65.6
62.8
11.3
63.8
66.4
10.5
62.0
70.2
9.7
60.1
74.2
8.9
41.0
71.4
56.8
13.5
69.7
60.0
12.5
67.9
63.4
11.6
66.1
67.0
10.8
64.2
70.8
9.9
62.3
74.8
9.2
43.0
74.0
57.3
13.8
72.2
60.5
12.9
70.3
63.9
11.9
68.5
67.5
11.1
66.5
71.3
10.2
64.5
75.4
9.4
45.0
76.6
57.8
14.2
74.7
61.0
13.2
72.8
64.4
12.3
70.8
68.0
11.4
68.9
71.9
10.5
66.8
75.9
9.7
47.0
79.2
58.4
14.6
77.3
61.5
13.6
75.3
64.9
12.6
73.3
68.6
11.7
71.2
72.4
10.8
69.1
76.5
10.0
49.0
81.9
58.9
15.0
79.9
62.1
13.9
77.9
65.5
12.9
75.8
69.1
12.0
73.6
73.0
11.1
71.5
77.1
10.2
51.0
84.6
59.5
15.3
82.6
62.6
14.3
80.5
66.1
13.3
78.3
69.7
12.3
76.1
73.6
11.4
73.9
77.7
10.5
53.0
87.4
60.1
15.7
85.3
63.2
14.6
83.1
66.6
13.6
80.9
70.3
12.6
78.6
74.2
11.6
76.3
78.4
10.8
55.0
90.3
60.7
16.1
88.1
63.8
15.0
85.8
67.3
13.9
83.5
70.9
12.9
81.2
74.9
11.9
78.8
79.0
11.0
YCUL0080EC
AIR TEMPERATURE ON CONDENSER (°F)
SST
(°F)
75°F
80°F
85°F
90°F
95°F
100°F
TONS
KW
EER TONS
KW
EER TONS
KW
EER TONS
KW
EER TONS
KW
EER TONS
KW
EER
35.0
71.4
61.3
12.6
69.8
64.6
11.7
68.1
68.1
10.9
66.4
71.9
10.1
64.5
76.0
9.3
62.6
80.4
8.6
37.0
74.1
61.8
13.0
72.4
65.1
12.1
70.6
68.6
11.2
68.8
72.5
10.4
66.9
76.6
9.6
64.9
80.9
8.9
39.0
76.8
62.3
13.3
75.0
65.6
12.4
73.2
69.2
11.6
71.3
73.0
10.7
69.4
77.1
9.9
67.3
81.5
9.2
41.0
79.6
62.9
13.7
77.7
66.2
12.8
75.8
69.8
11.9
73.9
73.5
11.0
71.9
77.7
10.2
69.7
82.1
9.4
43.0
82.4
63.4
14.1
80.5
66.7
13.1
78.5
70.3
12.2
76.5
74.1
11.3
74.4
78.2
10.5
72.2
82.7
9.7
45.0
85.3
64.0
14.5
83.3
67.3
13.5
81.3
70.9
12.6
79.2
74.7
11.7
77.0
78.8
10.8
74.8
83.2
10.0
47.0
88.3
64.6
14.8
86.2
67.9
13.9
84.1
71.4
12.9
81.9
75.3
12.0
79.7
79.4
11.1
77.4
83.8
10.2
49.0
91.4
65.2
15.2
89.2
68.5
14.2
87.0
72.0
13.2
84.7
75.9
12.3
82.4
80.1
11.4
80.0
84.4
10.5
51.0
94.5
65.8
15.6
92.2
69.1
14.6
89.9
72.6
13.6
87.6
76.5
12.6
85.1
80.7
11.7
82.7
85.1
10.8
53.0
97.6
66.4
16.0
95.3
69.7
14.9
92.9
73.3
13.9
90.5
77.1
12.9
88.0
81.3
12.0
85.5
85.8
11.1
55.0
100.9
67.1
16.4
98.4
70.3
15.3
96.0
73.9
14.3
93.4
77.8
13.3
90.9
81.9
12.3
88.3
86.4
11.4