SEQUENCE OF OPERATION

YCW With a Chilled Water Coil

The unit will respond to a cooling command from

the thermostat by powering a water control valve

open. The fan will operate at the speed selected at the

thermostat. When the space reaches the temperature

setpoint at the thermostat, the cooling valve will close

and the fan will continue to operate.

When using the T420 manual C/O thermostat and the

TB3-3/TB2-5 jumper is in place, the fan will con-

tinue to operate at the fan speed selected. Removing

the jumper will cause the fan to shut down when the

thermostat is satisfied.

When using the T200 thermostat, the stat will auto-

matically regulate the fan speed based on the differ-

ence between the space temp and setpoint -

@

4˚F off

setpoint, the fan will run

@

HI;

@

3˚F off setpoint, the

fan will run

@

MED;

@

2˚F off setpoint, the fan will

run

@

LO. When the thermostat is satisfied, the water

valve will be deenergized and the fan will revert to

LO speed.

The YCW-HW with Both a Chilled Water Coil and a

Hot Water Coil.

The unit control thermostat, on a call for heating, will

energize the hot water control valve. When the ther-

mostat is set for cooling, it will energize the chilled

water valve on a call for cooling. The fan will operate

at the speed selected at the thermostat. When the space

reaches the temperature setpoint at the thermostat, the

cooling valve will close (on cooling) or the heating

valve will close (on heating) and the fan will continue

to operate.

When using the T420 manual C/O thermostat and the

TB3-3/TB2-5 jumper is in place, the fan will con-

tinue to operate at the fan speed selected. Removing

the jumper will cause the fan to shut down when the

thermostat is satisfied.

When using the T421 auto C/O thermostat and the

TB3-3/TB2-5 jumper is in place, the fan will con-

tinue to operate at the fan speed selected. Removing

the jumper will cause the fan to shut down when the

thermostat is satisfied.

When using the T200 thermostat, the stat will auto-

matically regulate the fan speed based on the differ-

ence between the space temp and setpoint -

@

4˚F off

setpoint, the fan will run

@

HI;

@

3˚F off setpoint, the

fan will run

@

MED;

@

2˚F off setpoint, the fan will

run

@

LO. When the thermostat is satisfied, the water

valve will be deenergized and the fan will revert to

LO speed.

The YCWE With Both a Chilled Water Coil and

Electric Heating Coil.

The unit control thermostat, on a call for heating, will

energize the heater contactor(s). When the thermostat

is set for cooling, it will energize the chilled water

valve on a call for cooling. The fan will operate at

the speed selected at the thermostat. When the space

reaches the temperature setpoint at the thermostat,

the cooling valve will close (on cooling) or the heat-

ing contactors will open (on heating) and the fan will

continue to operate.

When using the T420 manual C/O thermostat and the

TB3-3/TB2-5 jumper is in place, the fan will con-

tinue to operate at the fan speed selected. Removing

the jumper will cause the fan to shut down when the

thermostat is satisfied.

When using the T421 auto C/O thermostat and the

TB3-3/TB2-5 jumper is in place, the fan will con-

tinue to operate at the fan speed selected. Removing

the jumper will cause the fan to shut down when the

thermostat is satisfied.

When using the T200 thermostat, the stat will auto-

matically regulate the fan speed based on the differ-

ence between the space temp and setpoint -

@

4˚F off

setpoint, the fan will run

@

HI;

@

3˚F off setpoint, the

fan will run

@

MED;

@

2˚F off setpoint, the fan will

run

@

LO. When the thermostat is satisfied, the water

valve will be deenergized (on cooling) or the heating

contactor will open (on heating) and the fan will revert

to LO speed.