MAINTENANCE

MOTOR

The blower motor should be cleaned annually and if it

has oiling ports, it should be oiled with a good grade

of SAE 20 oil. Normally a few drops of oil in each

bearing is sufficient.

COIL

The coil must be kept clean by any of the following

methods.

1. Cleaning with low-pressure compressed air.
2. Flushing or rinsing with water (a detergent is

advisable for greasy surfaces).

FILTERS

The intervals at which filters require replacement

depend on local conditions.

Because of dust and lint in the room, room-air filters

load up much more rapidly than outdoor-air filters.

Under normal conditions, the room air filter requires

replacement every six to eight weeks.

Clean or replace air filters regularly

Dirty filters reduce the air and heating

capacities of the unit. When the filters

are excessively dirty, the unit heating

capacity will be so reduced that it is in-

effective for heating the room. When

a room fails to heat, always check the

filters.

To ensure proper maintenance of the filters, it is best

to follow an organized maintenance procedure. The

following one is recommended:

Divide the total number of units on the job into six

equal groups. Each week inspect, clean or replace

the filters in each group, in rotation. This insures

a uniform servicing interval. The interval may be

lengthened or shortened as determined by experience.

If inspection shows only the room-air filter to be dirty,

this one alone should be replaced.

CLEAN UNIT INTERIOR

Once a year clean the fans and coils of the unit thor-

oughly. Remove the access panel as necessary.

Wipe the interior of the unit clean with a rag. Wipe

the motor and inside and outside of the fan housings.

(In cooling units, clean out the drain pan.)