beautypg.com

Prepare boiler location — clearances, Gold cgs gas-fired water boiler — boiler manual, Recommended service clearances – Weil-McLain GOLD CGS 550-110-260/0508 User Manual

Page 7: Required minimum clearances, Flooring, Foundation, Residential garage installations

background image

Part number 550-110-260/0508

7

GOLD CGs Gas-Fired Water Boiler — Boiler Manual

Prepare boiler location — clearances

1b

Figure 2

Required MINIMUM clearances

Figure 1

Recommended

SERVICE

clearances

(see

WARNING

below)

Recommended SERVICE clearances

(Fig. 1)

1. Provide clearances for cleaning and servicing the boiler and for

access to controls and components. See Figure 1 for recommenda-
tions.

2. Provide at least screwdriver clearance to jacket front panel screws

for removal of front panel for inspection and minor service. If
unable to provide at least screwdriver clearance, install unions and
shutoff valves in system so boiler can be moved for servicing.

Required MINIMUM clearances

(Fig. 2)

Never install the boiler in a space with clear-
ances less than the minimum clearances shown
in Figure 2

. Failure to comply can result in severe

personal injury, death or substantial property
damage and reduced boiler life.

1.

Hot water pipes:

at least

¹⁄₂

inch

from combustible material.

2.

Single-wall vent pipe:

at least 6 inches

from combustible mate-

rial.

3.

Type B double-wall metal vent pipe

: refer to vent manufacturer’s

recommendation for clearances to combustible material.

If any clearance is less than in Figure

1

, provide

openings for combustion and ventilation air
located on the wall or door opposite the boiler
FRONT (see Figure 2)

.

These openings must be located as shown in Figure 2 to provide
proper air fl ow around the boiler. The free area of each opening
(after deducting for louvers) must be at least

one square inch per

1,000 Btuh

of boiler input. If the building is of unusually tight

construction (see page 10 for defi nition), the air openings must
connect directly to outside or the building must have air openings
to the outside as specifi ed on page 10.
If clearances are equal to or greater than Figure 1, see pages 10
and 11 for location and sizing of combustion air openings.
Failure to comply can result in severe personal injury, death or
substantial property damage and reduced boiler life.

Flooring

The CGi boiler is approved for installation on combustible
fl ooring, but must never be installed on carpeting.

Do not install boiler on carpeting even
if foundation is used. Fire can result,
causing severe personal injury, death
or substantial property damage.

Foundation

1. Provide a solid brick or minimum 2-inch thick concrete

foundation pad if any of the following is true:
• fl oor can become fl ooded.

the boiler mounting area is not level.

2. Minimum dimensions are

25” length

by:

Minimum foundation width

CGs-3

15”

CGs-5

21”

CGs-4

18”

CGs-6

24”

Residential garage installations

Take the following special precautions when installing the
boiler in a residential garage. If the boiler is located in a
residential garage, per ANSI Z223.1:

Mount the boiler a minimum of

18 inches above the

fl oor

of the garage to assure the burner and ignition

devices will be no less than 18 inches above the fl oor.

• Locate

or

protect the boiler

so it cannot be damaged

by a moving vehicle.