beautypg.com

Service & maint. — annual start-up, Cleaning boiler heating surfaces, Gold cgs gas-fired water boiler — boiler manual – Weil-McLain GOLD CGS 550-110-260/0508 User Manual

Page 42: Review with owner

background image

Part number 550-110-260/0508

42

GOLD CGs Gas-Fired Water Boiler — Boiler Manual

Service & maint. — annual start-up

10b

Review with owner

1. Review the

User’s Information Manual

with the

owner.

2. Emphasize the need to perform the maintenance

schedule specified in the

User’s Information

Manual

(and in this manual as well).

3. Remind the owner of the need to call in a licensed

contractor should the boiler or system exhibit any
unusual behavior.

4. Remind the owner to follow the proper shutdown

procedure and to schedule an annual start-up at the
beginning of the next heating season.

Cleaning boiler

heating

surfaces

The boiler contains ceramic fi ber
and fi berglass materials. Use care
when handling these materials per
instructions on

page 64

of this

manual. Failure to comply could
result in severe personal injury.

1. Shut down boiler:

• Follow

To Turn Off Gas to Appliance

instructions on boiler and

Operating instruc-

tions

.

Do not drain boiler unless it will be exposed
to freezing temperatures. If using antifreeze in
system, do not drain.

2. Follow shutdown procedure.

3. Remove venting system connection to boiler.

4. Remove top jacket panel. Turn back insulation.

5. Remove collector box/transition assembly. Clean

sealant from assembly and sections.

6. Remove radiation plates hanging between sec-

tions.

7. Remove burners from base. Brush and vacuum

burners to remove all dust and lint. Verify that all
burner ports are free of debris.

8. Place newspapers in base of boiler to collect soot.

9. Clean between sections with wire fl ue brush.

10. Remove newspaper and soot. Vacuum or brush base

and surrounding area.

11. Reinstall radiation plates.

12. Replace collector box/transition assembly. Seal with

sealant. Obtain gas-tight seal to prevent fl ue gas
spillage and carbon monoxide emissions, resulting
in severe personal injury or death.

13. Replace insulation and jacket top panel.

14. Start up boiler following Section

7

of this manual

and the boiler

Operating instructions

(Section

9c

of this manual). Excessive sooting indicates im-
proper gas combustion. If found check for proper
combustion and make any necessary adjustments.