Connect water boiler piping

(continued)

7

3. Piping for multiple boilers (see Figure 13):

A

Size secondary boiler pump GPM based on
following formulas:

Calculate only secondary piping circuit resistance.
Boiler resistance will be about equal to three 90
degree elbows of secondary pipe size. Operate each
boiler and its secondary pump from a Weil-McLain
boiler control panel. Do not maintain boiler at
predetermined water temperature.

B

Primary pump GPM and head calculation should
not include secondary boiler circuits. Primary
pump can operate continuously during heating
season.

C

Space 12" maximum or as close as practical.

D

Check valve.

E

Hand valve.

Expansion tank(s), relief valves and other accessories are
required but not shown.

Figure 13 Multiple water boiler piping

Temperature rise, °F = 230°F – Return water temperature

Gross output is in Btuh.

= GPM

Gross output

Temperature rise x 500