Piping connections – Weil-McLain EG User Manual

Page 11

background image

Part Number 550-110-639/0703

11

EG, PEG, EGH G

AS

-

FIRED

B

OILERS

SERIES

4 — B

OILER

M

ANUAL

Piping connections

(continued)

2

Figure 15

Recommended piping connections
EGH steam boilers

Figure 14

Recommended piping connections
EG steam boilers

Steam boilers

1. Refer to table and Figures 14 or 15. Pipe exactly as

shown. Satisfactory operation of a steam heating
system depends on adequate condensate return to
boiler to maintain a steady water level. Avoid adding
raw make-up water. Where condensate return is not
adequate, install low water cut-off and pump control,
condensate receiver, and condensate boiler feed pump.
Refer to Figure 16 for sizing.

2. Install steam relief valve vertically in “E” tapping.

Relief valve discharge piping must be piped
near floor close to floor drain to eliminate
potential or severe burns. Do not pipe to
any area where freezing could occur. Do
not plug, valve or place any obstruction in
discharge line.

3. EGH only - install 3/4" system blow-off (drain) valve

in lowest part of return piping close to boiler.

Figure 16

Condensate receiver capacity

NOTE : Steam supply must be on same end as controls. Return may be from

either end.