beautypg.com

Troubleshooting guide, Control – VistaQuest N7227V5 User Manual

Page 78

background image

– 78 –

TROUBLESHOOTING GUIDE

(continued)

SYMPTOM

POSSIBLE CAUSE

REMEDY

7. Intrusion alarm for no ap-

parent reason. (continued)

7d. Magnetic contacts improperly connected or

wire broken.

7e. Entry door programmed as “Instant”

7f.

Loose fitting door or window being rattled
by wind or vibrations.

7d. Check wiring connections. Be sure wires

are properly stripped and are tightly
fastened to screw terminals.

7e. Check and revise programming. Re-

program transmitter number.

7f

Mount magnet closer to magnet.

8. Repeated low battery signal.

8a. Transmitter located where temperature

drops below 32

°

F.

8b. Poor quality or unspecified battery in

transmitter.

8c.

Transmitter malfunctioning.

8a. Change location. Use magnetic contacts to

protect opening.

8b. Check battery. Use only batteries specified

in the instructions (does not apply to
transmitters with non-replaceable
batteries).

8c. Replace faulty transmitter.

9. Local bell and keypad sound

continuously after arming.

9.

Exit or interior zone contained a fault at end
of Exit Delay (e.g., Exit door left open).

The "Exit Alarm" display, etc. will also
result if an alarm from an exit or interior
zone occurs within two minutes after the
end of an exit delay.

→

9a. If system disarmed

before ensuing entry

time runs out, "CA" or "Canceled Alarm"
will be displayed. Sounding will stop.

9b. If system

not disarmed before entry time

ends, "EA" or "Exit Alarm" will be displayed
and Exit Alarm message will be sent to
central station. Sounding will continue until
system is disarmed or timeout occurs.

Clear display by entering code + OFF a second
time. Avoid fault when re-arming.

CONTROL

SYMPTOM

POSSIBLE CAUSE

REMEDY

1. "POWER" light off or

“NO AC” displayed

1a. Interrupted AC power supply.

1a. Check transformer connection and power

line circuit breaker.

2. Digital communicator mes-

sage not being received.

2a. Control in TEST mode.

2b. Telephone connection not secure.

2c.

Digital communicator malfunctioning

2d. Telephone number in program needs prefix

or access code.

2e. Telephone call to central monitoring station

requires operator assistance.

2a. Remove from TEST mode.

2b. Check all connections.

2c.

Check with a different VISTA–10SE.

2d. Program prefix or access code into the

control

2e. System cannot work in this situation.

3. Does not arm properly.

3a. READY light not on.

3a. Check for faulted zone(s) by pressing [

] ;

make faulted zone(s) intact, or use
Bypass arming, if desired.

4. VISTA–10SE doesn't respond

to keystrokes on keypad.

4a. "CC" or "MODEM COMM" displayed.

4b. "d1" or "System Busy" displayed.

4c.

"E4" or "E8" displayed.

4d. Keypad address setting incorrect.

4a. System is in communication with down-

loader at central station. Wait until down-
load session is finished.

4b. System has just been powered and is in

its one minute initialization. To bypass
this time, press '#' + '0'.

4c.

More zones have been programmed than
the zone expansion modules can handle.
Delete some zones or use a higher
capability RF receiver.

4d. Keypads must be set for address 31 (non-

addressable mode).

S M O K E D E T E C T O R

SYMPTOM

POSSIBLE CAUSE

REMEDY

1. Detector alarms, no apparent

reason.

1a. Dust, dirt in sensing chamber.

1b. Improper location.

1c.

Unit malfunctioning.

1a. Clean unit's sensing chamber with vacuum

cleaner per unit's instructions.

1b. See unit's instructions for locations to

avoid. Relocate as necessary.

1c.

Replace detector.

2. Detector's siren sounds.

2a. Unit not receiving required power.

2b. Unit malfunctioning.

2a. Check for proper installation of battery. Try

new battery.

2b. Replace detector.