VistaQuest N7227V5 User Manual
Page 20

– 20 –
Zone Types
00 = Zone Not Used
01 = Entry/Exit #1
02 = not used
03 = Perimeter
04 = Interior Follower
05 = Trouble Day/Alarm Night
06 = 24 Hr Silent
07 = 24 Hr Audible
08 = 24 Hr Aux
09 = Fire
10 = Interior w/Delay
20 = Arm Stay*
21 = Arm-Away*
22 = Disarm*
23 = No Alarm
Response
* 5800 RF Systems only
When the display shows the zone type you
want, press [
✱
] to continue.
You must enter “00” as the zone type for any hard-wired zones that are not
used.
02 Report Code
1st 03 2nd 12
3C
The report code consists of 2 hexadecimal
digits, each in turn consisting of 2 numerical
digits. For example, for a report code of "3C",
enter [0][3] for "3" and [1][2] for "C". Refer to the
SYSTEM COMMUNICATION section f o r
complete information on report codes, if
necessary.
Enter the desired report code and then press [
✱
]
to continue.
Typical summary display
Zn ZT – RC
In
L
02
03
– 3C
HW: –
A summary display will appear, showing the
data for the zone that was just programmed.
If it is programmed satisfactorily, press [
✱
] to
continue.
Program Alpha?
0 = No 1 = Yes
0
The next request is to enter Alpha descriptors
for the zones. The entry may be done now
(enter 1), or may be done at a later time using
✱
82 interactive mode (enter 0). See the
ALPHA
DESCRIPTOR PROGRAMMING section for
specific procedure.
Enter Zn Num.
(00 = Quit)
03
Enter next zone number
↑
If “0” (no) was entered above, the system will
return to the Enter Zone Number prompt.
Proceed with the programming for the next
zone, i.e., [
✱
] and zone number.
Programming Panic Keys
When programming zones, note the following:
The defaults for individual panic keys or panic key pairs are:
Zone 07.
✱
& #, or
B: zone type 06 (24-hr silent).
Zone 95. 1 &
✱
, or A: zone type 00 (not used).
Zone 96. 3 & #, or C: zone type 00 (not used).
Panic keys are programmed (or re-programmed) by keying the zone number,
e.g.,
✱
07,
✱
95, and
✱
96, and entering the desired zone type that will provide
the desired panic function for each of these keys, using the list of zone types
below.
06 = 24 Hr Silent
07 = 24 Hr Audible
08 = 24 Hr Aux
09 = Fire