beautypg.com

VistaQuest N7227V5 User Manual

Page 29

background image

– 29 –

Data field

22 RF SYSTEM TYPE, must have been programmed for a 5700

RF system (“1”). Also, the House ID should have been entered in field

24,

and all 5700 transmitters set to the same House ID.

4. Press

56. (Zone Programming Mode)

Use this mode to program zone numbers, zone types, and alarm report
codes for all 5700 wireless zones that are going to be used in the system.
5700 transmitters are programmed into the system one at a time, starting
with the lowest Zone/ID number that has been assigned to it previously via
its DIP switches.
Example:

If the first transmitter to be programmed has been set via its DIP

switches to Zone/ID 20, you will program zone types, and alarm report
codes for that transmitter in zone 20.

En te r Zn Nu m .

( 0 0 = Q u it)

2 0

Zone 20 entered

5. Enter the zone number that you wish to

program. As an example, zone 20 is shown
entered here.
Zone

numbers between 10 and 63 can be

assigned to transmitters. However, the total
number of wireless zones that can be used is 8
for 5700 RF systems (see Table

1 on a

previous page).

Zn ZT – R C I n : L

2 0 0 0 –

– :

6.

A summary display will appear, showing the
status of that zone's program.
If it is programmed satisfactorily, press [#] to
back up one step and enter another zone
number, if desired.
If the zone is not programmed, or you want to
change it, press [

]. A prompt for Zone Type

will appear.

Zone Number

2 0 Zo n e T ype

P e r im e te r

0 3

Entry for Zone Type

03 shown

7. Each zone must be assigned a zone type,

which defines the way in which the system
responds to faults in that zone.

Enter the zone type (or change it, if necessary).
Zone types that you can assign are listed below.
Enter the desired zone type code as listed.

A detailed explanation of
each zone type is provided
in

the ZONE RESPONSE

TYPE DEFINITIONS
section in the separate
Programming Guide.

00 = Zone Not Used
01 = Entry/Exit Burglary
03 = Perimeter
04 = Interior Follower
05 = Trouble Day/Alarm Night
06 = 24 Hr Silent

07 = 24 Hr Audible
08 = 24 Hr Aux
09 = Fire
10 = Interior w/Delay
23 = No Alarm
Response

When the display shows the zone type you
want, press [

] to continue.

2 0 R e po r t Co de

1 st 0 3 2 n d 1 2 3 C

8. Enter the report code.

The report code consists of 2 hexadecimal
digits, each in turn consisting of 2 numerical
digits. For example, for a report code of "3C",
enter [0][3] for "3" and [1][2] for "C".
See the

SYSTEM COMMUNICATIONS section

for complete information on report codes, if
necessary.
Press [

] to continue.

2 0 I n pu t De vic e

R F T r a n s. R F :

9. For the hardwired zones (HW), and the zones

for a 5700 sys tem's transmitters (RF), the Input
Device types are automatically assigned (Panic,
Duress, and Tamper inputs are not applicable).