Univex 5100-02-IT User Manual
Page 21
Model 5100-02-IT Combustible Gas Sensor Module
Page: 19
5.2 MAIN
MENU
Table 5-1 describes the primary human-machine interface operation.
Table 5-2 describes the operational display values of the human-machine interface system.
ID
THE DISPLAY SHOWS
“S
TART
”
INSTEAD OF
“S
TARTING
,
THE MODULE MUST BE CALIBRATED BEFORE USING IT
.
Table 5 - 1: Master Menu
Display
Description
STARTING
Warm-up at start-up
##%LEL
Concentration
L ##%LEL
Low Alarm (Warning)
H ##%LEL
High Alarm (Alarm)
HIGH
>100% Full Scale
NO SENSR
Sensor Failure
C ##%LEL
Calibration Mode
ACK
Acknowledged Function
Table 5 - 2: Operation Display Values
Function
Display
Description
Reference
M
E
M
E
M E
M E
M
E
M
E
M
E
M
E
M
E
M
E
M
E
Key
Mode
Switch [M]
Enter
Switch [E]
Up
Switch [▲] Previous Menu
Down
Switch [▼] Next Menu
5100-02
First screen at power up-model
1.Xxa
VX.Xxx
Second screen at power up-version
Warm.XXX
Third screen at start up-warm up
0%LEL
Normal condition - default display
Mode
ALMRSET:
Mode Function -Alarms Acknowledge
SSSSSSSS
Banner: Use
0%LEL
Default Display
Mode
ALMRSET:
Mode Function - Alarms Reset
Mode
CALIB:
Mode Function - Calibrate
Table 6-1
Mode
SETUP:
Mode Function - Module Set-up
Table 5-3
Mode
MAINT:
Mode Function - Maintenance
Table 5-4
Mode
EXIT-?
Exit Mode
Enter
0%LEL
Apply Selected Mode (Exit)
0%LEL
Default Display