[A05] Error Piping freeze prevention control

Water heat

exchange control board

DPSW11-1 is ON

Replace backup heater
and safety valve

Set water heat board
DPSW11-1 to ON

No

(Backup heater NG)

Backup heater terminal

has 230ACV ( ± 23V)

Power is connect to

built-in heater terminal

Yes

Yes

Restart

TWI 4, TWO 4, or

THO 4 is detected

Circulation pump keeps

being energized or 3 minutes

passed after the start

No

No

Place power cable for
backup heater

Set breaker for backup heater
to ON, or Check indoor
electronic wiring

No

Backup heater element

is conductive

Yes

Replace TWI, TWO,
and THO sensors

No

(See characteristic table in page 101)

TWI, TWO, THO

sensor characteristics

are correct

Yes

Yes

Replace water heat

exchange control board

+00A09-002_01EN_SVM_ALL_Air_to_Water.book Page 78 Monday, October 5, 2009 2:09 PM