Function code table

FC

Item

Details

First shipment

01

Water heat exchanger capacity

0012: 802XWH**-E
0017: 1402XWH**-E

Depends on type

02

Cooling/Non-cooling switching

0000: Cooling

0001: No cooling

0001: No cooling

07

Hot water HP operation mode upper time limit

0000: 0 mins

-

0120: 120 mins

0030: 30 mins

08

Hot Water Boost operation time

0003: 30 mins

-

0018: 180 mins

0006: 60 mins

09

Hot Water Boost set temperature

0040: 40°C

-

0080: 80°C

0075: 75°C

0A

Anti bacteria set temperature

0070: 70°C

-

0080: 80°C

0075: 75°C

0B

Anti bacteria holding time

0000: 0 mins

-

0060: 60 mins

0030: 30 mins

0C

Mixing valve drive time

0003: 30 secs

-

0024: 240 secs

0006: 60 secs

18

Upper limit of cooling set temperature

0018: 18°C

-

0030: 30°C

0025: 25°C

19

Lower limit of cooling set temperature

0010: 10°C

-

0018: 18°C

0010: 10°C

1A

Upper limit of heating (ZONE1) set temperature

0037: 37°C

-

0055: 55°C

0055: 55°C

1B

Lower limit of heating (ZONE1) set temperature

0020: 20°C

-

0037: 37°C

0020: 20°C

1C

Upper limit of heating (ZONE2) set temperature

0037: 37°C

-

0055: 55°C

0055: 55°C

1D

Lower limit of heating (ZONE2) set temperature

0020: 20°C

-

0037: 37°C

0020: 20°C

1E

Upper limit of hot water set temperature

0060: 60°C

-

0080: 80°C

0075: 75°C

1F

Lower limit of hot water set temperature

0040: 40°C

-

0060: 60°C

0040: 40°C

20

Hot water HP start temperature

0020: 20°C

-

0045: 45°C

0038: 38°C

21

Hot water HP stop temperature

0040: 40°C

-

0050: 50°C

0045: 45°C

22

Priority mode Hot water supply/Heating switching
temperature

-0020: -20°C

-

0020: 20°C

0000: 0°C

23

Priority mode Boiler/Heat pump switching temperature -0020: -20°C

-

0020: 20°C

-0010: -10°C

24

Outside air temperature for hot water temperature
correction start

-0020: -20°C

-

0010: 10°C

0000: 0°C

25

Hot water temperature correction value

0000: 0K

-

0015: 15K

0003: 3K

26

Night set back change temperature range

0003: 3K

-

0020: 20K

0005: 5K

27

Set temperature shift with heating Auto

-0005: -5K

-

0005: 5K

0000: 0K

29

Outside air temperature T1 temperature

-0015: -15°C

-

0000: 0°C

-0010: -10°C

2B

Outside air temperature T3 temperature

0000: 0°C

-

0015: 15°C

0010: 10°C

2C

Set temperature A with outside air temperature of -
20°C

0020: 20°C

-

0055: 55°C

0040: 40°C

2D

Set temperature B with outside air temperature of T1

0020: 20°C

-

0055: 55°C

0035: 35°C

2E

Set temperature C with outside air temperature of 0°C

0020: 20°C

-

0055: 55°C

0030: 30°C

2F

Set temperature D with outside air temperature of T3

0020: 20°C

-

0055: 55°C

0025: 25°C

30

Set temperature E with outside air temperature of 20°C

0020: 20°C

-

0055: 55°C

0020: 20°C

31

Zone2 ratio with Zone1 as Auto

0000: 0%

-

0100: 100%

0080: 80°C

33

Heater control down time

0000: 5 mins
0002: 15 mins

0001: 10 mins
0003: 20 mins

0001: 10 mins

34

Heater control up time

0000: 10 mins
0002: 30 mins

0001: 20 mins
0003: 40 mins

0000: 10 mins

3A

Frost protection function Yes/No

0000: No

0001: Yes

0001: Yes

3B

Frost protection set temperature

0010: 10°C

-

0020: 20°C

0015: 15°C

3C

Water 2-way energization (logical reverse) control

0000: No

0001: Yes (Reverse)

0000: No

3E

Heating HP/Boiler priority switching when using boiler

0000: Priority on HP

0001: Priority on boiler

0000: Priority on HP