beautypg.com

Toshiba HWS-802XWHT6-E User Manual

Page 134

background image

133

Toshiba

13

Flow switch

1. How to remove

1) Perform the step 1-1 and step 5.
2) Remove the flow switch.

2. How to attach

1) Attach a new flow switch in the reverse order of the

removal.

Note1)

As shown on the right,
place a flow sensor parallel to the water heat
exchanger inlet pipe so that the wire is place on
the right side from the front view.

14

Manometer

1. How to remove

1) Perform the step 1-1 and step 5 and 6.
2) Remove the manometer.

No.

Exchange parts name

Work procedure

Remarks

To replace a water circuit part, first close the water
supply source valve and the valve of water pipe
connected to the hydro unit.

The flow switch connection uses an O ring for water
seal. Be careful not to scratch the O ring; otherwise,
water leakage may occur.

After the flow switch replacement repair, open the
water supply source valve and water piping valve to
pass water through the hydro unit, and check that
the flow switch connection has no water leakage.

Flow switch

Flow switch

Water heat inlet pipe

To replace a water circuit part, first close the water
supply source valve and the valve of water pipe
connected to the hydro unit.

After the manometer replacement repair, open the
water supply source valve and water piping valve to
pass water through the hydro unit, and check that
the manometer connection has no water leakage.

Manometer