2.3. Description of terminals

Terminal

symbol

Function

Electrical specifications

Internal circuits

NETA
NETB

L

ON

W

ORKS

transmission

data / reception data

no polarity

SHLD

L

ON

W

ORKS

communication

shield terminal.

This terminal is not
connected to other circuits in
this board.

G/E

Grounding terminal

Connect to network ground

NETA

NETB

SHLD

FT-X1

Spark

gap

G/E

F

R

Multifunctional programmable
contact input.

SINK/SOURCE can be
selected with SW1.

No voltage contact input
24V

DC

, 5mA or less

N.B. Use contact parts for low

current.

F, R

CC

P24

4.7k

P24

PTC

SOURCE

SINK

820

VIB

Multifunction programmable
analog input.
with internal pull-up resistor
for PTC

0 to 10V

DC

input

Using this terminal as PTC
input, set SW1 to PTC side
and set the parameters
(f645 and f646) to
proper value.

VIB

15k

VIB

P10

PTC

15k

3.3k

CC

Control circuit’s equipotential
terminal

P24

24 V

DC

power supply output

24V

DC

-50mA

P24

P24

PTC

FLA
FLB
FLC

Multifunctional programmable
relay contact outputs

1c contact
30V

DC

-0.5A

250V

AC

-1A (cos

φ =1

250V

AC

-0.5A (cos

φ =0.4)

FLA

FLB

FLC

Ry

Danger

Prohibited

Do not change switches settings while the power is on.

It may lead to electric shocks or damage.

Mandatory

Turn off the motor operation signals before setting the parameter and the switch
(SW1), when changing the VIB function. Otherwise, the motor may suddenly
start and that may result in injuries.