Troubleshooting checklist – Trane WPWD User Manual

Page 28

background image

28

WSHP-SVX02A-EN

Troubleshooting

Checklist

Problem

Heating

Cooling

Cause

Correction

No response to any
thermostat setting

X

X

Main power off

Check fuses

X

X

Defective control transformer

Replace

X

X

Broken or loose connection

Repair

X

X

Defective thermostat

Replace

X

X

Transformer

Reset Transformer

Unit short cycles

X

X

Thermostat or sensor improperly located

Relocate

Insufficient capacity

X

X

Low on refrigerant charge

Locate leak, repair and recharge by
weight (not by superheat)

X

X

Restricted thermal expansion valve

Replace

X

X

Defective reversing valve

See WSHP-IOM-# for touch test chart

X

X

Thermostat improperly located

Relocate

X

X

Unit undersized

Recalculate heat gains/losses

X

X

Inadequate water flow

Increase GPM

X

X

Scaling in heat exchanger

Clean or replace

X

Water too hot

Decrease temperature

X

Water too cold

Increase temperature

High pressure switch open

X

Inadequate GPM

Increase water flow to unit

X

Water too hot

Decrease temperature

X

X

Overcharged with refrigerant

Decrease charge

X

X

Defective pressure switch

Check or replace

High head pressure

X

Trash in heat exchanger

Backflush

X

Low water flow

Increase GPM

X

X

Overcharge of refrigerant

Decrease charge

X

X

Non-condensable in system

Evacuate and recharge by weight

X

X

Water too hot

Decrease temperature

Low suction pressure

X

X

Undercharged

Locate leak, repair and recharge

X

X

Restricted thermal expansion valve

Repair / replace

X

Inadequate GPM

Increase GPM

Low Pressure switch open

X

Inadequate GPM

Increase GPM

X

Water too cold

Increase temperature

X

X

Undercharged with refrigerant

Increase charge

X

X

Defective pressure switch

Replace

X

X

Heat transfer fluid too cold

Raise water temperature. For smaller
tonnage units, switch pressure switch
wires from 35 psig to 7 psig

Freezestat open

X

Inadequate GPM

Increase GPM

X

Water too cold

Increase GPM

X

X

Defective freezestat

Replace freezestat

X

Heat transfer fluid too cold

Replace freezestat. For smaller tonnage
units, switch pressure wires from 35 psig
to 7 psig.