Operating pressures – Trane WPWD User Manual
Page 22

22
WSHP-SVX02A-EN
Operating Pressures
Table OP-1: Cooling mode operating pressures
Unit Size
Entering
Load
(Degree F)
Entering Source Temperature (Degree F)
50
86
104
Suction
Pressure
Discharge
Pressure
Suction
Pressure
Discharge
Pressure
Suction
Pressure
Discharge
Pressure
EXWA 240
53.6
46-56
103-143
49-59
188-228
49-59
238-278
EXWA 240
86
61-71
111-151
84-94
205-245
87-97
259-299
Table OP-2: Heating mode operating pressures
Unit Size
Entering
Load
(Degree F)
Entering Source Temperature (Degree F)
50
68
104
Suction
Pressure
Discharge
Pressure
Suction
Pressure
Discharge
Pressure
Suction
Pressure
Discharge
Pressure
EXWA 240
75
46-56
160-200
65-75
170-210
86-96
183-223
EXWA 240
104
49-59
245-285
68-78
254-294
94-107
268-308
EXWA 240
122
49-59
310-350
68-78
320-360
95-105
333-373
Operating Pressures