beautypg.com

Operating pressures – Trane WPWD User Manual

Page 22

background image

22

WSHP-SVX02A-EN

Operating Pressures
Table OP-1: Cooling mode operating pressures

Unit Size

Entering

Load

(Degree F)

Entering Source Temperature (Degree F)

50

86

104

Suction

Pressure

Discharge

Pressure

Suction

Pressure

Discharge

Pressure

Suction

Pressure

Discharge

Pressure

EXWA 240

53.6

46-56

103-143

49-59

188-228

49-59

238-278

EXWA 240

86

61-71

111-151

84-94

205-245

87-97

259-299

Table OP-2: Heating mode operating pressures

Unit Size

Entering

Load

(Degree F)

Entering Source Temperature (Degree F)

50

68

104

Suction

Pressure

Discharge

Pressure

Suction

Pressure

Discharge

Pressure

Suction

Pressure

Discharge

Pressure

EXWA 240

75

46-56

160-200

65-75

170-210

86-96

183-223

EXWA 240

104

49-59

245-285

68-78

254-294

94-107

268-308

EXWA 240

122

49-59

310-350

68-78

320-360

95-105

333-373

Operating Pressures