beautypg.com

Installation power wiring, Warning, Caution – Trane WPWD User Manual

Page 16: Live electrical components, Use copper conductors only, Hazardous voltage

background image

16

WSHP-SVX02A-EN

Field Installed Power Wiring
Power wiring to the equipment must
conform to National and Local Electric
Codes (NEC) by a professional electri-
cian.

WARNING

Live Electrical

Components!

During installation, testing, ser-

vicing and troubleshooting of this

product, it may be necessary to

work with live electrical compo-

nents. Have a qualified licensed

electrician or other individual

who has been properly trained in

handling live electrical compo-

nents perform these tasks. Failure

to follow all electrical safety pre-

cautions when exposed to live

electrical components could re-

sult in death or serious injury.
Verify that the power supply available
is compatible with the unit’s name-
plate. Use only copper conductors to
connect the power supply to the unit.

CAUTION

Use Copper

Conductors Only!

Unit terminals are not designed

to accept other types of conduc-

tors. Failure to use copper con-

ductors may result in equipment

damage.

Main Unit Power Wiring
A field supplied disconnect switch
must be installed at or near the unit in
accordance with the National Electric
Code (NEC latest edition).
Location of the applicable electric ser-
vice entrance for HIGH (line voltage)
may be found on the unit submittal at
the front of this manual (pages 7
through 9).

The high voltage connection is made
at the 1TB1 terminal block for the 20-
ton equipment, and at 1K1 for the 2-
ton through 6-ton equipment. The ter-
minal block or contactor is located in-
side the unit control box. Refer to the
customer connection diagram that is
shipped with the unit for specific ter-
mination points.
Provide proper grounding for the unit
in accordance with the local and na-
tional codes.
Control Power Transformer
The 24-volt control power transform-
ers are to be used only with the acces-
sories called out in this manual.
Transformers rated greater than 50 VA
are equipped with internal circuit
breakers. If a circuit breaker trips, turn
OFF all power to the unit before at-
tempting to reset it.

WARNING

Hazardous Voltage!

Disconnect all electric power, in-

cluding remote disconnects be-

fore servicing. Follow proper

lockout/tagout procedures to en-

sure the power can not be inad-

vertently energized. Failure to

disconnect power before servic-

ing could result in death or seri-

ous injury.

The transformer is located in the
control box.

Installation

Power Wiring

This manual is related to the following products: