17

Controls Using 24 VAC
Before installing any wire, refer to the
electrical access locations on the unit
submittals located on pages 7 through
9.
Ensure that the AC control wiring be-
tween the controls and the unit’s ter-
mination point does not exceed three
(3) ohms/conductor for the length of
the run.
Note: Resistance in excess of 3-ohms
per conductor may cause component
failure due to insufficient AC voltage
supply.
Check all loads and conductors for
grounds, shorts, and mis-wiring.
Use copper conductors unless other-
wise specified.
Do not run the AC low voltage wiring
in the same conduit with the high volt-
age power wiring.

Low voltage connection diagrams are
shown in Figure 9. Optional desuper-
heater fuse installation shown in Fig-
ure 10
.

Table 4: 24V AC conductors

Distance

from unit to Control

Recommended

Wire Size

000-460 feet

18 gauge

461-732 feet

16 gauge

733-1000 feet

14 gauge

Table 5: Deluxe controller diagnostic LEDs

Color: Green

Color: Red

Controller Mode

LED1

LED2

LED3

OFF

OFF

OFF

Control OFF

ON

OFF

OFF

Normal/Compressor OFF

ON

OFF

FLASH

Anti-short Cycle

ON

OFF

ON

Normal/Compressor ON

FLASH

ON

OFF

Brownout Condition

ON

FLASH

ON

Soft Lockout (low pressure)

ON

FLASH

FLASH

Soft Lockout (high pressure)

ON

ON

ON

Manual Lockout (low pressure)

ON

ON

FLASH

Manual Lockout (high pressure)

ON

FLASH

OFF

Manual Lockout (condensate overflow)

ON

ON

OFF

Compressor Disable

Installation

Low Voltage Wiring

Figure 9: Low voltage connection

Figure 10: Desuperheater fuse installation