Maintenance, Warning hazardous voltage, Warning hazardous chemicals – Trane WPWD User Manual

Page 25

background image

WSHP-SVX02A-EN

25

Preventive Maintenance
Maintenance on the unit is simplified
with the following preventive sugges-
tions:

WARNING

Hazardous

Voltage!

Disconnect all electric power, in-

cluding remote disconnects be-

fore servicing. Follow proper

lockout/tagout procedures to en-

sure the power can not be inad-

vertently energized. Failure to

disconnect power before servic-

ing could result in death or seri-

ous injury.

Check the contactors and relays within
the control panel at least once a year.
It is good practice to check the tight-
ness of the various wiring connections
within the control panel.
A strainer (60 mesh or greater) must
be used on an open loop system to
keep debris from entering the unit heat
exchanger and to ensure a clean sys-
tem.
For units on well water, it is important
to check the cleanliness of the water-
to-refrigerant heat exchanger. Should
it become contaminated with dirt and
scaling as a result of bad water, the
heat exchanger will have to be back
flushed and cleaned with a chemical
that will remove the scale. This service
should be performed by an experi-
enced service person.

Maintenance

WARNING

Hazardous

Chemicals!

Coil cleaning agents can be either

acidic or highly alkaline. Handle

chemical carefully. Proper han-

dling should include goggles or

face shield, chemical resistant

gloves, boots, apron or suit as re-

quired. For personal safety, refer

to the cleaning agent manufactur-

ers Materials Safety Data Sheet

and follow all recommended safe

handling practices. Failure to fol-

low all safety instructions could

result in death or serious injury.
It should be noted that the water qual-
ity should be checked periodically. See
Table 9.

Table 9: Water Quality Table

Scaling

Calcium and magnesium
(total hardness)

Less than 350 ppm

Corrosion

pH

7-9.5

Hydrogen Sulfide

Less than 1 ppm

Sulfates

Less than 25 ppm

Chlorides

Less than 125 ppm

Carbon Dioxide

Less than 75 ppm

Total dissolved solids
(TDS)

Less than 1000 ppm

Biological Growth

Iron Bacteria

Low

Erosion

Suspended Solids

Low