Toshiba RELIABILITY IN MOTION 1000 User Manual
Page 50

27
LIMITATIONS AND EXCLUSIONS
1.
This limited warranty shall not cover the UPS, UPS parts, or BATTERY during their
respective warranty periods, if the following storage, maintenance, installation, operating
conditions are not met throughout the warranty periods (5 conditions below):
Valve Regulated Lead Acid (VRLA) Batteries for Toshiba UPS Required Operating, Installation, and
Maintenance Conditions
1. Temperature
Annual Average Temperature is to be 77
°F (25°C) with no greater
temperature of 89
°F (32°C) for more than 30 days
Maximum Number of Cycles (24 Months)***
Discharge Time
Battery > 9AHr
Battery < 9AHr
30 min
20
69
15 min
25
86
10 min
32
110
5 min
38
130
2. Maximum # of Full
Charge/Discharge
Cycles
*** > 9AHr Typically extended runtimes < 9AHr Typically Single Phase
Systems.
3. Storage
While UPS is in Transit or in storage, it must always be in a suitable
temperature (as stated above)
4. External Battery
Parallel battery string applications must be approved by TIC in writing
5. Idle Batteries
User must recharge the batteries if not in use (charged) for more than 6
months
Credit for Replacement Battery When Approved Warranty
Time from Shipments
UPS Batteries
Cost to Customer
Months
% Credit
% List Price
0-24 100
0
25-30 55
45
31-36 45
55
37-42 35
65
43-48 25
75
49-54 15
85
55-60 5
95