Toshiba VF-nC1 User Manual
Page 23

E6581090
A-14
1
• Operate in areas where ambient temperature ranges from -10°C to 50°C. However, when
installing the inverter where the ambient temperature will rise above 40°C, detach the caution
label on the top surface.
5cm
5cm
5cm
Measurement
position
Measurement
position
Note: The inverter is a heat-emitting body. Make sure to provide proper space and ventilation
when installing in the cabinet. When installing the inverter in a cabinet, you are
recommended to detach the caution label even if the temperature in the cabinet is below
40°C.
• Do not install in any location that is subject to large amounts of vibration.
• If the VF-nC1 Inverter is installed near any of the equipment listed below, provide measures to
insure against errors in operation.
Solenoids:
Attach surge suppressor on coil.
Brakes:
Attach surge suppressor on coil.
Magnetic contactors: Attach surge suppressor on coil.
Fluorescent lights:
Attach surge suppressor on coil.
Resistors:
Place far away from VF-nC1
Inverter.
Resistor