Toshiba's JKSSS7 series complies with EEMAC,
NEMA, UL and CSA standards and is available for
induction, synchronous and wound rotor configurations.
The JKSSS7 series is available in the following en-
closed ratings:
600 & 720 Amps, 2300-4800 Volts, Up to 6,000 HP

Continuous Current

Short Circuit & Withstand Capability

Approximate Maximum Horsepower Based on Continuous Current

SOLID STATE STARTER

JKSSS7+ Series

Protective Features

Electronic Overload:

Retentive Thermal Memory w/Dynamic Reset Memory

Phase Imbalance/Single Phase

Short Circuit

Ground Fault - Optional

RTD Temperature

Phase Reversal/Phase Sequence

Overcurrent

Starts-per-Hour

Shorted SCR

Undercurrent/Loss of Load

Starter Overtemperature

Shorted SCR

Undervoltage

Overvoltage

Microprocessor Digital Control Unit (DCU) **
Programming Keypad:
Operator Control
System/Motor Protection
Serial Communication (RS485)
Statistical Data
LCD status and alarm display with Twelve LEDs

POWER - Indicates control power is present

RUN - Indicates unit/motor is running
ALARM - Lights in conjunction with AUX 2 to
indicate event or warn of possible critical condition
TRIP - Lights in conjunction with AUX 1 to
indicate a critical condition has occurred.
AUX 1-8 - Auxiliary unit relays

** Standard on all JKSSS4+ & JKSSS7+ models, 200-720A, 2300-6900V

Metering

**

Percent of FLA
Phase Current (A, B & C)
Average Current
Ground Fault Current (w/Optional GF
Protection)
Remaining Thermal Register
Thermal Capacity to Start
Average Start Time
Average Start Current
Measured Capacity to Start
Time Since Last Start
Line Frequency
Phase Order
Motor RPM
kW, kVA, kVAR, PF, MWHr
kW Demand, kVA Demand, kVAR
Demand, Amps Demand - (All Date/
Time Stamped)

** Standard on all JKSSS4+ & JKSSS7+
models, 200-720A, 2300-6900V

Additional Features

Serial Communication Port:
RS485 or RS422 with Modbus RTU Protocol or
RS485 or RS422 with Windows Interface
Rugged Gate Firing Circuit Using Ring Transformer
Opto-isolated Inputs

Enclosure Type

Maximum Continuous

Amperes*

One-High Controller

Type 1 Ventilated

720

Type 1 Non-Ventilated

650

Type 12 & 3R

600

Interrupting

Capacity

(Symmetrical

Amperes)

Interrupting

Capacity

(Symmetrical

MVA)

Short Time

Capability

30 Seconds

(Amperes)

Short Time

Capability

1 Second

(Amperes)

Dielectric

Withstand

1 Minute

(kV)

Impulse

Voltage

Withstand

(kV)

50,000

@ 2.3 - 4.6 kV

200 @ 2.3 kV
350 @ 4.0 kV
400 @ 4.6 kV

4320

10,800

AC 13.25

DC 19

60

Maximum Horsepower at Utilization Voltage

2300 Volts, 3 Phase

4200 Volts, 3 Phase

0.8 PF 1.0 PF

0.8 PF 1.0 PF

720

3000 3500

3000

5500 6000

5500

650

2750 3000

2750

5000 5500

5000

600

2500 2750

2500

4500 5000

4500

Enclosed

Maximum

Continuous

Current

(Amperes)

Induction

Motors

Synchronous

Motors

Induction

Motors

Synchronous

Motors