beautypg.com

Solid state starter, Jksss4+ series – Toshiba XT JK Series User Manual

Page 3

background image

Toshiba's JKSSS4 series complies with EEMAC,
NEMA, UL and CSA standards and is available in
non-reversing and reversing, multi-speed, synchro-
nous and wound rotor configurations.

The JKSSS4 series is available in the following
enclosed ratings:
360 Amps Max.
2300-6900 Volts

Short Circuit & Withstand Capability

Approximate Maximum Horsepower Based on Continuous Current

SOLID STATE STARTER

JKSSS4+ Series

z

Electronic Overload:

Retentive Thermal Memory
Dynamic Reset Memory

z

Phase Imbalance/Single Phase

z

Short Circuit

z

Ground Fault - Optional

z

RTD Temperature

z

Phase Reversal/Phase Sequence

z

Overcurrent

z

Starts-per-Hour

z

Shorted SCR

z

Undercurrent/Loss of Load

z

Starter Overtemperature

z

Shorted SCR

z

Undervoltage

z

Overvoltage

Protective Features

Continuous Current

Enclosure Type

Max. Continuous Amps*

90" One-High Controller

Type 1 Ventilated

360A

Type 12 Ventilated w/

Fans & Type 12 Filters

310A

Type 1 Non-Ventilated

300A

Type 12 & 3R

300A

Interrupting

Capacity

(Symmetrical

Amperes)

Interrupting

Capacity

(Symmetrical

MVA)

Short Time

Capability

30 Seconds

(Amperes)

Short Time

Capability

1 Second

(Amperes)

Dielectric

Withstand

1 Minute

(kVAC)

Impulse

Voltage

Withstand

(kV)

50,000

@ 2.3 - 6.6 kV

200 @ 2.3 kV
350 @ 4.0 kV
400 @ 4.6 kV
570 @ 6.6 kV

2400

6000

18.2

60

2300V

4200V

6600V

0.8 PF 1.0 PF

0.8 PF 1.0 PF

0.8 PF 1.0 PF

360

1500 1750

1500

2500 3000

3000

4000 5000

4500

320

1250 1500

1250

2250 2500

2500

3500 4000

4000

300

1000 1250

1000

2000 2500

2250

3000 3500

3500

Synchronous

Motors

Induction

Motors

Enclosed

Maximum

Continuous

Current

(Amperes)

Maximum Horsepower at Utilization Voltage

Synchronous

Motors

Induction

Motors

Synchronous

Motors

Induction

Motors

If UL or CUL is required,
specify when ordering.
Consult Factory for
applicable models and
options.