Solid state starter, Jksss4+ series – Toshiba XT JK Series User Manual

Page 2

background image

The low voltage section is oversized and is at a
convenient height. This section is isolated from
the medium voltage section.
Digital Control Module
LCD Display (two lines) and Status LEDs
(Power, Run, Alarm, Aux. Relays)
Programming Keypad (Non-volatile Memory)

Isolated Low Voltage Compartment

Visible, Bolted Pressure, Isolation Switch

Less Resistance
Less Wear
Zero Insertion Pressure
Mechanical Interlocking System

Adjustments

Motor Full Load Ampere (FLA)
Dual Adjustments - Two independent settings
Initial Voltage 0 - 100% of nominal voltage
Current Limit 200 - 500% of motor FLA
Acceleration Time 1 - 120 seconds
Deceleration Time 1 - 60 seconds
Three custom Accel curves
Jog: 5 - 100% Volt., 1 - 20 sec., Current 100 - 500%
Kick Start: 10 - 100% Voltage, 0.1 - 2 sec.
Coast Down (Back Spin) Lockout Timer 1 - 60 min.
Starts-per-Hour Lockout Timer
1 - 10 successful starts per hour
1 - 60 min. between start attempts
Undercurrent 10 - 90% (with adjustable trip delay
1 - 60 sec.)
Overload Reset - Selectable Manual or Automatic
Two 4 - 20 mA Analog Outputs: Selectable from
Off, RPM, Hottest Non-Stator RTD, Hottest Stator
RTD, RMS Current, % of Motor Load

The JKSSS Series of motor starter is the result of
extensive research and development. This
streamlined, space saving design (only 30" wide)
provides the ultimate in maintenance ease and
safety features. These medium voltage solid state
starters are available for the control of induction,
wound rotor or synchronous motors, up to 6.9kV.
All starters are designed to meet NEMA Class E2
requirements.

Features

Soft Start

125% Continuous Duty
500% - 60 Seconds, 600% - 30 Seconnds
30" Wide Footprint
Digital Microprocessor Control
LCD Display w/Programming Keypad

Toshiba Medium Voltage Vacuum Contactors,

for Bypass and Input Isolation

Incoming, 400A JK Disconnect Switch - Bolted

Pressure Switch Connections

Current Limiting, High Interrupting Capacity,

"R" Rated Motor Starting Fuses

Two Stage Solid State Motor Protection

Starting: Programmable for Class 5 through 30
Running: Programmable for Class 5 through 30

Control Power Transformers with Primary and

Secondary Fuses

NEMA Type 1 Enclosure

Separate Medium and Low Voltage Compartments

Mechanical and Electrical Interlocks

SOLID STATE STARTER

JKSSS4+ Series

Options

Maintenance Data

If UL or CUL is required, specify when ordering.
Consult Factory for applicable models and options.

Drawout Input Isolation, Vacuum Contactor
NEMA Type 12 or 3R Enclosure
1200 or 2000A Main Copper Bus
Available in MCC Lineups with Other JK Series

Starters (FVNR, FVR, RVAT, Synchronous, Etc.)

Available in MCC Lineups with Main Incoming

Disconnect Switch or Toshiba Vacuum
Circuit Breaker

The soft start is available as a controller only for

users which already have an existing full voltage
starter (disconnect switch, main power fuses &
contactor) and wants to add reduced voltage
starting and soft stop features.

PFC Contactor - Vacuum contactor for switching

Power Factor Correction Capacitor.

Manual (Full Voltage) Bypass Selection with solid

state protection (2E) or bimetallic overload.

Fault indications: Shorted SCR, Phase Loss, Shunt

Trip, Phase Imbalance, Phase Rotation, Overload,
Overtemp, Overcurrent, Short Circuit, Load Loss,
Ground Fault, Stator Phase Trip, RTD Trip, or Any Trip

Coast Down Time

Starts per Hour

Time Between Starts

Event History - Up to 60 events. Data includes

cause, date, time, phase and ground current.

Additional Features

Serial Communication Port:
RS485 or RS422 with Modbus RTU Protocol or
RS485 or RS422 with Windows Interface
Rugged Gate Firing Circuit Using Ring Transformer
Opto-isolated Inputs
Auxiliary Contacts - Form C, 5A @ 240Vac max.